Technical data

General data

4
Technical data
General data
Field
Order designation
Communication medium
Network topology
Number of stations
Max. cable length
PROFINET stations
PNO identification no.
Device identification
(device ID)
Baud rate
Switching method
Switch latency
Voltage supply
Conformities, approvals
,
"Servo Drives 9400" hardware manual
Here you can find the ambient conditions and the electromagnetic
compatibility (EMC) specifications applying to the communication module.
36
Values
E94AYCER
CAT 5e
Tree, star and line
Max. 255 in the subnetwork
100 m
IO device with real time communication features (RT)
0x0106
hex
0x9400
hex
100 Mbps
"Store−and−forward"
Approx. 125
s for maximum telegram length
External supply via separate power supply unit
l
"+": U = 24 V DC (20.4 V...28.8 V), I = 130 mA
l
"−": reference potential for external voltage supply
l
CE
l
EAC
l
UL
l
EDK94AYCER DE/EN/FR/ES/IT 6.1