Electrical installation

External voltage supply

External voltage supply
)
Note!
In the case of an external voltage supply and for greater distances between the
control cabinets, always use a separate power supply unit (SELV/PELV) that is
safely separated in accordance with EN 61800−5−1 in each control cabinet.
The external voltage supply of the communication module is necessary if PROFINET
communication is to continue in the event that the power supply to the standard device is
cut off.
Supply the communication module via the 2−pole plug connector (X240) with a separate
supply voltage.
Designation
+
Terminal data
Field
Electrical connection
Possible connections
Stripping length
44
Description
External voltage supply
U = 24 V DC (20.4 V ... 28.8 V)
I = 130 mA
Reference potential for external voltage supply
Values
2−pin plug connector with spring connection
rigid:
flexible:
9 mm
l
2
1.5 mm
(AWG 16)
without wire end ferrule
2
1.5 mm
(AWG 16)
with wire end ferrule, without plastic sleeve
2
1.5 mm
(AWG 16)
with wire end ferrule, with plastic sleeve
2
1.5 mm
(AWG 16)
EDK94AYCER DE/EN/FR/ES/IT 6.1