External DC voltage supply
If necessary, supply the communication module with a separate 24 V DC voltage using
a two-pole plug connector. ±10 % .
Use a separate supply unit in every control cabinet if the distance between the control
cabinets is larger than normal.
Plug connector
+
-
Controller
820X
821X / 822X / 824X /
93XX / 9300 Servo
PLC / Drive PLC
8200 vector
Connection terminals
Electrical connection
Possible connections
Tightening torque
Bare end
L
-15-
Designation
Vcc24
GND24
External voltage supply
Always required.
Only necessary if the mains which supply the corresponding controllers is
to be switched off but the communication must not be interrupted.
You can use the internal power supply for these controllers.
See information in "internal DC voltage supply" ^ 34
Plug connector with threaded terminal end
0.5 ... 0.6 Nm (4.4 ... 5.3 lb-in)
6 mm
EDKMF2141 DE/EN/FR 2.0
Electrical installation

DC voltage supply

Explanation
External supply 24 V DC ± 10 % , 120 mA
Reference potential for external voltage supply
2
rigid: 1.5 mm
(AWG 16)
flexible:
without wire crimp cap
2
1.5 mm
(AWG 16)
with wire crimp cap, without plastic sleeve
2
1.5 mm
(AWG 16)
with wire crimp cap, with plastic sleeve
2
1.5 mm
(AWG 16)