Protection against uncontrolled
) ) ) )
Note!
After a fault (e.g. short-term mains failure) a restart of the drive is not
always wanted.
l
By setting L-C0142 = 0, the drive can be inhibited if
– the corresponding controller sets a "fault message"
– the fault is active for more than 0.5 s
Parameter function:
l
L-C0142 = 0
– Controller remains inhibited (even if the fault is not active any longer)
– The drive restarts in a controlled mode: LOW-HIGH transition at one
of the inputs for "Controller inhibit" (CINH, e.g. at terminal X5/28)
l
L-C0142 = 1
– Uncontrolled restart of the controller possible
L
restart-19-
EDKMF2141 DE/EN/FR 2.0
Commissioning
Initial switch-on
5