Commissioning
5
Initial switch-on
Configuration for communication with the fieldbus module
82XX /
1. The drive can be controlled through LON, if the Lenze parameter "Operating mode"
8200
(C0001) is changed from 0 to 3. This change can be made by using the keypad or
vector
directly via LON.
l
Example:
For LON Write (C0001=3), subindex: 0, value = 30000.
2. Terminal 28 (controller enable) is always active and must be HIGH for LON operation
(see the corresponding Operating Instructions). Otherwise, the controller cannot be
enabled by the LON.
3. 821X, 8200vector and 822X:
The QSP function (quick stop) is always active.
During LON operation one of the input terminals configured for QSP (Lenze setting:
not assigned) must be HIGH (see Operating Instructions for the controller).
4. The controller now accepts control and parameter-setting data from the LON.
93XX
1. If you want to control the drive via LON, configure the Lenze parameter "Signal
configuration" (C0005) for xxx3. This change can be carried out using the 9371BB
keypad or the LON. Select the signal configuration 1013 for first commissioning.
l
Example:
For LON Write (C0005=1013), subindex: 0, value: 10130000.
2. Set the parameter C0142 to 0.
Please read the next TIP for code C0142.
3. Terminal 28 (RFR = controller enable) is always active and must be HIGH for LON
operation (see Operating Instructions for the controller). Otherwise, the controller
cannot be enabled by the LON.
4. With the signal configuration C0005=1013, the QSP function (quick stop) and the
CW/CCW changeover are assigned to the input terminals E1 and E2, and thus they
are always active.
E1 must be HIGH for LON operation (see 93XX Operating Instructions).
With the signal configuration C0005=xx13, terminal A1 is configured as voltage
output. Therefore, only the following terminals must be connected via cables:
l
X5.A1 with X5.28 (ctrl. enable)
l
X5.A1 with X5.E1 (CW/QSP)
5. The controller now accepts control and parameter-setting data from the LON.