External Voltage Supply - Lenze L-force EtherCAT EMF2192IB Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6
Electrical installation

External voltage supply

External voltage supply
)
Note!
Always use a separate power supply unit in every control cabinet and safely
separate it according to EN 61800−5−1 ("SELV"/"PELV") in the case of external
voltage supply and larger distances between the control cabinets.
The external voltage supply ...
ƒ is necessary if EtherCAT communication is to be maintained when the standard
device is switched off.
ƒ is provided via the 2−pin terminal strip with screw−type connection (24 V DC).
Terminal
+
Terminal data
Area
Electrical connection
Possible connections
Tightening torque
Stripping length
44
Description
External voltage supply
U = 24 V DC (20.4 V − 0 % ... 28.8 V + 0 %)
I = 85 mA
Reference potential for external voltage supply
Values
Plug connector with screw connection
rigid:
flexible:
0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in)
6 mm
l
2
1.5 mm
(AWG 16)
without wire end ferrule
2
1.5 mm
(AWG 16)
with wire end ferrule, without plastic sleeve
2
1.5 mm
(AWG 16)
with wire end ferrule, with plastic sleeve
2
1.5 mm
(AWG 16)
EDK2192IB DE / EN / FR 2.0

Publicité

Table des Matières
loading