6
Electrical installation

Synchronisation of the standard device

Synchronisation of the standard device
The synchronisation of the standard device via the EtherCAT fieldbus ˘ if it is supported ˘
can be carried out via the 3−pin plug connector with screw connection (sync).
)
Note!
ECS servo system
For the ECS axis modules, a synchronisation with operating system
ƒ
software version ³ 8.3 is possible.
For the ECS power supply module a synchronisation is not supported.
ƒ
Wire ...
ƒ terminal "0" to the corresponding sync input of the standard device (see
documentation of the standard device).
ƒ the sync supply to the 24V supply of the communication module or the standard
device.
W
EtherCAT-
Sync
Terminal
+
0
42
Opto
Description
External sync supply (SELV/PELV)
U = 24 V DC (20.4 V − 0 % ... 28.8 V + 0 %)
Sync output
m
(t = 150
s, I
max
Reference potential for external sync supply
l
0
= 10 mA at 24 V)
2192ECAT002
EDK2192IB DE / EN / FR 2.0