Electrical installation

Assignment of the terminals

Assignment of the terminals
Terminal
Designation
X3.1/
E1
Digital inputs *)
E2
20
39
GND2
59
7
GND1
*) Alternatively frequency input 0 ... 10 kHz (one−track) or 0 ... 1 kHz (two−track) configuration via C0425
60
Function / level
Adapt the individual setting via C0007 or C0410.
l
Input resistance: 3.3 k
l
0 = LOW (0 ... +3 V DC) PLC level, HTL
l
1 = HIGH (+12 ... +30 V DC) PLC level, HTL
(reference: GND2)
DC voltage source for the internal supply of the digital inputs E1 and
E2
l
+20 V DC (reference: GND1)
l
I
= 20 mA
max
Reference potential of the
l
digital inputs at X3.1/E1 and X3.1/E2
l
controller inhibit (CINH) at X3.2/28
External DC voltage supply for the function module
±
l
+24 V DC
10% (reference: GND1)
l
Current consumption on 24 V DC: 80 mA
The current for looping through the supply voltage to other nodes
via terminal 59 must be max. 3 A.
Reference potential for X3.1/20 and X3.2/20
l
W
EDK82ZAFPC−201 DE/EN/FR 7.0