Lenze E82ZAFPC201 Instructions De Montage page 61

Profibus i/o
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Terminal
Designation
X3.2/
+
PES
A
T/R(A)
B
T/R(B)
CN
CNTR
VP
40
GND3
7
GND1
39
GND2
28
CINH
20
59
*) E.g. for repeater connection
EDK82ZAFPC−201 DE/EN/FR 7.0
Function / level
Additional HF shield termination
RS485 data line A
RS485 data cable B
For function see PROFIBUS standard *)
l
Level during data transmission: CNTR = HIGH
(+5 V DC, reference: GND3)
For function see PROFIBUS standard *)
l
U = +5 V DC (reference: GND3)
l
I
= 10 mA
max
Reference potential for PROFIBUS network *)
Reference potential for X3.1/20 and X3.2/20
Reference potential of the
l
digital inputs at X3.1/E1 and X3.1/E2
l
controller inhibit (CINH) at X3.2/28
Controller inhibit
l
Start = HIGH (+12 ... +30 V DC)
l
Stop = LOW (0 ... +3 V DC)
(reference: GND2)
DC voltage source for internal supply of controller inhibit (CINH)
l
+20 V DC (reference: GND1)
l
I
= 20 mA
max
External DC voltage supply for the function module
±
l
+24 V DC
10% (reference: GND1)
l
Current consumption on 24 V DC: 80 mA
The current for looping through the supply voltage to other nodes
via terminal 59 must be max. 3 A.
l
Electrical installation
Assignment of the terminals
6
61