Commissioning
Commissioning steps
Step
Description
10.
Use C1510 to assign the process data output words of the standard
device to the process data input words (PIW) of the master.
Lenze setting:
PIW10: Ramp function generator input (NSET1−RFG1−IN)
11.
Enable process output data with C1512 = 65535.
l
Only required if C1511 has been changed.
l
Do not deactivate the process data words used by setting the
respective subcodes of code C1511 = 0.
l
The value in C1512 is volatile and all process data are enabled
after every switch−on.
12.
Enable the standard device via terminal 28 (CINH).
l
Set terminal 28 to HIGH level.
13.
Select the setpoint.
l
The master transmits the setpoint via the selected process data
output word.
14.
Change to the READY TO SWITCH ON state:
l
The master transmits the DRIVECOM control word:
0000 0000 0111 1110
15.
The standard device in the READY TO SWITCH ON state.
l
The master receives the DRIVECOM status word:
xxxx xxxx x01x 0001
16.
Change to the OPERATION ENABLED state.
l
The master transmits the DRIVECOM control word:
0000 0000 0111 1111
17.
The drive starts up.
66
PIW1: DRIVECOM status word (DRIVECOM STAT)
PIW2: Output frequency with slip (MCTRL1−NOUT+SLIP)
PIW3: Output frequency without slip (MCTRL1−NOUT)
PIW4: Apparent motor current (MCTRL1−IMOT)
PIW5: Actual process controller value (PCTRL1−ACT)
PIW6: Process controller setpoint (PCTRL1−SET1)
PIW7: Process controller output (PCTRL1−OUT)
PIW8: Controller load (MCTRL1−MOUT)
PIW9: DC−bus voltage (MCTRL1−DCVOLT)
(007E
bin
bin.
(007F
bin
).
hex
).
hex
l
Detailed
information
EDK82ZAFPC−201 DE/EN/FR 7.0