Electrical installation

Assignment of the terminals

Assignment of the terminals
Terminal
Designation
X3 1/
CG
CAN−GND
CL
CAN−LOW
CH
CAN−HIGH
Terminal
Designation
X3 2/
59
7
GND1
Terminal
Designation
X3 3/
7
GND1
39
GND2
28
CINH
20
62
Function / level
Reference potential for CAN
CAN data line (LOW)
CAN data line (HIGH)
Function / level
External DC voltage supply for the function module
±
l
+24 V DC
10% (reference: GND1)
l
Current consumption at 24 V DC: 80 mA
The current flowing to other bus nodes via terminal 59 when looping
through the supply voltage must not exceed 3 A.
Reference potential for X3.3/20
Function / level
Reference potential for X3.3/20
Reference potential 2 of the controller inhibit (CINH) at X3.3/28
Controller inhibit
l
Input resistance: 3.3 k
l
Start = HIGH (+12 ... +30 V)
l
Stop = LOW (0 ... +3 V)
(reference: GND2)
DC voltage source to the external supply of the controller inhibit
(CINH)
l
+20 V (ref: GND1)
l
I
= 10 mA
max
l
W
EDK82ZAFUC010 DE/EN/FR 5.0