Taconova ES 5941 Manuel D'utilisation page 85

Régulateur d'eau fraîche
Masquer les pouces Voir aussi pour ES 5941:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ES 5941
LEG04
MAN.
Manual
TERM.DISIN-
thermal disin-
FECTION
fection
LEG05
THM.DISINF.
Time program
TIMEPRO-
for thermal
GRAM
disinfection
Adjuster is visible if RECHARGING PRIMARY NAC00 (08:100) is set to on.
NAC
RECHARGING
NAC00 RECHARGING
Option: Thermal recharging request (see above for
PRIMARY
basic parameters)
NAC03 SWITCH ON
Switch-on
RECHARCHIN
hysteresis for
G
the tank set-
point tem-
perature
NAC04 TO SENSOR
TO tank top
TYPE
sensor selec-
tion, sensor
type
NAC09 RECHARGE
Time program
TIME PRO-
for domestic
GRAM
water
Adjuster is visible if WARM HOLDING FUNCTION WHF00 (05:113) is set to on.
WHF
WARM
HOLDING
FUNCTION
WHF00 WARM
Option:
HOLDING
Standby/
FUNCTION
warm holding
function
WHF01 MIN SWITCH
Min. switch
OFF TIME
off time
WHF02 MAX
Min. switch
SWITCH ON
on time
TIME
KOM
COMMUNI-
CATION
KOM01 LANGUAGE
SELECTION
Operating instructions
32
Time program for enabling the
legionella protection function
If the temperature in the tank is >
setpoint plus setting, a charging
request is ended.
n
0: NTC 5K
n
1: PT 1000
n
2: 0...5 V
Time program for activating
domestic hot water preparation at
the normal setpoint or for acti-
vating recharging.
(see above for basic parameters)
The warm holding function is
blocked for the set time if the min-
imum switch-on time has elapsed or
if the flow temperature is reached.
The warm holding function is
switched off once the set time has
elapsed of if the flow temperature is
reached.
Info and menu parameters
on/off
-
25
-
-
25
on/off
off
1...30
K
0 ...2
-
25
-
-
25
on/off
off
25
0...60
min. 25
0...30
min. 25
0...8
-
0
04/2021 Item no. 215790 EA no. 1321
05:084
05:062
08:063
28:066
05:061
05:113
36:040
36:041
04:056