Electrical Connection - Taconova ES 5941 Manuel D'utilisation

Régulateur d'eau fraîche
Masquer les pouces Voir aussi pour ES 5941:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ES 5941
2.2

Electrical connection

Operating instructions
8
DANGER!
The mains voltage connections on the left-hand side
L/L'/1–5/N are loaded with 230 volts. These termi-
nals must only be touched when they are de-ener-
gised. Otherwise, there is a danger of death due to
electric shock.
eBUS connection and sensor lines are to be installed
in a separate location from power lines.
The connection assignment is dependent on, and
varies according to, the chosen hydraulic variant and
option. This is marked by "*".
About installation:
n
The strain relief (cable clamps) can be installed normally or con-
versely depending on the cable strength used. This is done to ach-
ieve optimum safeguarding of the wiring.
n
The electrical installation and safeguarding are to comply with
local regulations.
n
The controller is to be continuously energised in order to ensure
its function at all times.
n
For this reason, upstream mains switches are to be limited to
emergency or main switches, which are usually left in the oper-
ating position.
n
Prior to commissioning, all components are to be checked to
ensure that the electrical connection has been established prop-
erly.
With regard to highly inductive loads in the vicinity of
the controller (contactors, solenoid valves, etc.),
interference suppression by means of RC modules
directly at the coil connections of the interfering
components may be necessary. Recommended RC
modules: 0.047 mF, 100 W for 250 VAC (e.g. Bosch,
RIFA, etc.).
Assembly and connection
04/2021 Item no. 215790 EA no. 1321