Commissioning
Calibration of the flow rate
Measures after commissioning
04/2021 Item no. 215790 EA no. 1321
In order for all functions to operate flawlessly, calibration of the flow
rate in the circulation line is always to be carried out when using a
circulation pump. ZIR 06 CIRC. CALIBRATION (
of the circulation volume" on page 39 ).
n
Check that all temperature setpoints are set correctly.
n
Check that it is possible to take a reading of the temperatures
(actual values) of the connected sensors.
n
Check that the temperatures (actual values) of the connected
sensors are plausible.
n
Check that hot water preparation is possible by means of a tapping
process.
n
Enter setting specific to the hydraulic variant or adjustment of the
controller.
Operating instructions
ES 5941
Ä Chapter 6.5 "Calibration
13