Operating instructions
28
n
TKW
0: NTC 5K
domestic
n
1: PT 1000
cold water
n
2: 0...5 V
sensor selec-
tion, sensor
type
n
Circulation
0: Off
pump func-
n
1: Continuously ON and time
tion
program
n
2: Temperature and time pro-
gram
n
3: Pulse switching and time
program
Adjuster KAS07 for definition in
the cascade, pump, centrally or
locally
Option:
Function for layering the return
Return flow
temperature in the buffer. This
switch
setting activates the function
and the effective direction of the
changeover valve is reversed.
n
-1: Relay closes when TPR is
hot (for tank at top)
n
0: Option OFF
n
1: Relay closes when TPR is
cold (for tanks at bottom)
Thermal dis-
The domestic hot water is heated
infection
to the set legionella protection
function
temperature once as per the set-
ting. This temperature is main-
tained for the minimum hold time.
n
0: no function
n
1: Disinfection activated
n
2: Circulation support
In the cascade, depending on the
adjuster KAS07:
KAS07=0: Thermal disinfection to
be defined locally at each station
and carried out.
KAS07=1: Thermal disinfection to
be defined centrally at each sta-
tion at which the circulation
pump is installed. Thermal disin-
fection is carried out centrally for
all stations.
Option:
Recharging requirement for
Thermal
recharging/charging the primary
recharging
energy tank.
requirement
Info and menu parameters
0...2
-
25
0...3
-
0
-1...1
0
0
0...2
-
0
on/off
0
04/2021 Item no. 215790 EA no. 1321
36:017
05:006
05:110
05:014
08:110