2.7.3 Mobile application

The generating sets are intended to operate while stationary. They may not be installed on a vehicle or other mobile equipment
unless a study has been carried out analysing the various installation and usage specifications. It is prohibited to use the generating
set whilst it is in motion. If earthing is not possible, connect the generating set's earth terminal to the vehicle earth.
2.7.4 Connection and choice of cables
For all connections, use flexible, strong rubber-sheathed cable which complies with standard IEC 60245-4 or equivalent cables, and
ensure that they are kept in perfect condition. Only use one class I electrical device per socket and connect equipment to the
generating set using a cable equipped with a PE protective conductor (green/yellow); this protective conductor is not required for
class II equipment. Adhere to the cross sections and lengths recommended in this table during installation or when using electrical
extensions.
Generating set type:
Generating set socket type:
Recommended cable cross section:
Length of
51 to 100 m
cable used
101 to 150 m*
*This cable length is the maximum permitted length, and must not be exceeded.
Installation method = cables on raceway or non-drilled tablet/Permitted drop in voltage = 5%/Multi-core conductors/Cable type PVC
70°C (e.g. H07RNF)/Ambient temperature =30°C.
2.8
Risks during handling operations, use and maintenance
For safety reasons, all operations must be carried out by staff with the necessary skills and using suitable equipment. Maintenance
must be carried out regularly and properly using only original or equivalent parts. Gloves must be worn.
Safety guidelines for handling petroleum products:
DANGER
Safety guidelines for handling batteries:
DANGER
10 A
mm²
AWG
0 to 50 m
4
10
10
RISK OF EXPLOSION
Respect the local regulations in force concerning the handling of petroleum products.
Filling should be carried out with the engine switched off and cold. Smoking, using a
naked flame or producing sparks are forbidden while the fuel tank is being filled. After
filling, always check that the tank's filler cap is properly tightened. Clean any traces of
fuel with a clean cloth and wait until the vapours have dispersed before starting the
generating set.
The fluids used by generating sets, such as oils and fuels, are dangerous products.
Never ingest them. Avoid prolonged or repeated contact with the skin.
RISK OF POISONING OR EXPLOSION
Follow the battery manufacturer's recommendations. Use insulated tools
only. Never use sulphuric acid or acid water to top up the electrolyte level.
Never leave the battery close to a flame or fire. Always ensure adequate
ventilation during charging.
Single phase
16 A
mm²
AWG
mm²
10
6
9
10
7
10
7
25
7
16
5
35
Three-phase
32 A
10 A
AWG
mm²
AWG
7
1.5
14
3
2.5
12
2
4
10
16 A
mm²
AWG
2.5
12
4
10
6
9