Note the following points when connecting the charging
station:
 Each charging station must be connected using a
separate residual current circuit breaker (residual current
circuit breaker type A for single-phase versions, residual
current circuit breaker type B for three-phase versions).
 No other circuits may be connected to this residual
current circuit breaker.
 For versions Start E, Standard E and Basic E, the residual
current circuit breaker (RCCB) must be provided on site.
 For versions Start E, Standard E, Basic E und Basic R, the
circuit breaker (CB) must be provided on site.
Design of the on-site circuit breaker
Danger
Fire hazard due to device overload.
Fire hazard due to device overload in case of wrong design
of the on-site circuit breaker.
The nominal current of the selected circuit breaker must
not exceed the specifications on the nameplate.
The EU versions of the devices (Start E, Standard E, Basic E
and Basic R) are supplied without integrated circuit breakers.
The circuit breakers must be scaled according to the
specifications on the name plate, the configuration switch
settings, the supply line (line length, cable cross-section) to
the charging station and national regulations.
 See Chapter 6.1.1 "Setting the charging current upper
limit" on page 15.

5.5.3 Terminals

Fig. 14: Terminals for the supply line (example)
Connect the supply line:
1. Strip the supply cable over a length of 370 mm and
remove the core insulation over a length of 12 mm.
2.
Connect the cores
2
terminal block
according to the circuit diagram. The
1
protective earth conductor (PE) must be longer than all
other conductors!
3. Check that the individual cores are properly connected
and that the screws are tightened.
of the supply cable to the
14