Information according to DIN EN 179 and DIN EN 1125
!
Warning!
Danger to do modification of doors along escape routes: The safety features of this product are an
essential requirement for its conformity with EN 179 and EN 1125. No changes or modifications may be
made, which are not described in these instruction.
Unsuitable doors diminish personal safety and intrusion protection: Only approved and technically
faultless doors are suitable for the mounting of the electric security lock 809. Prior to the mounting of the
electric security lock 809, the door must be inspected to ensure that it closes properly and is not warped.
The door must be approved for the use of the electric security lock 809. Operating elements of the doors
may not interfere with each other.
The electric security lock 809 is not permitted for use on double acting swing doors or double-leaf doors.
Unsuitable locks reduce personal safety and fire safety: The electric security lock 809 is suitable for fire
doors or smoke protection doors . Check whether the certification of the door matches the lock. Make
sure that the electric security lock 809 is installed in the appropriate size and with the suitable accessories.
Unsuitable door seals reduce personal safety: None of the functions of the electric security lock 809 may
be impaired with the use of door seals (e.g. profile seals or bottom seals).
Shattering glass doors can cause severe injury: Glass doors or glass parts on doors must be made of
safety glass or composite safety glass.
Unsuitable fastening means diminish personal safety and intrusion protection: Suitable fastening
means must be used depending on the installation situation and materials of the door.
Incorrect or faulty mounting diminish personal safety: The normal installation height for the horizontal
push rod is 900 mm to 1100 mm above the finished floor surface. If the majority of persons in the building
are children, the installation height must be reduced accordingly.
The horizontal push rod must be installed such that greatest possible effective bar length is achieved.
Any lock provided counterparts or coverings must be installed in order to ensure conformity with this
European Standard.
Limited moveability of the door diminishes personal safety: All blocking elements must be mounted
such that the free movement of the door is not impeded. The doors may only be locked with the approved
locks. No additional devices may be installed. Any installed door closers may not impair the actuation of
the door by children and infirm persons.