Télécharger Imprimer la page

Installation Self-Test And Reading Out Error Codes; Network Monitoring Function - ABB i-bus EIB Mode D'emploi

Masquer les pouces Voir aussi pour i-bus EIB:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 19

Installation self-test and reading out error codes

The installation self-test checks the connection and wiring of
EIB Delta-Meters. The installation self-test is carried out
automatically approx. every 8 seconds. If device or installation
errors occur, they are reported on the LCD display with the
"Error" group signal.
Error codes which describe the type of device or installation
error can either be read out in 'Alternative mode' or Menu mode
[3 Error ]. A description of the error codes and notes on
remedying them can be found on the following pages.
Important: So that the EIB Delta-Meters can successfully carry
out the installation self-test, the meter must be
connected with all the phases and there must be a
load current of at least 100 mA per phase in the
secondary circuit.
30
Important: The following descriptions regarding the operation of
the software outline the sequence of push button
actions starting from 'Normal mode'. The descriptions
should be used in connection with the software menu
diagram.
In Menu mode [3 Error ], the following error codes are
displayed.
Button Number Display/comment
Normal mode (starting position).
x 1
[3 Error ]
S
x 1
Error codes are displayed automatically.
S
If no error occurs, the text [no Err ] is
displayed.
x n
Scrolls manually through the individual errors.
Sc
x 1
Back to [3 Error ]
LSc
x 1
Back to Normal mode.
LSc
Network monitoring function and reading out
the electrical measured variables
All electrical measured variables, which are measured with the
EIB Delta-Meter in order to record the energy consumption, can
be indicated on the LCD display either in 'Instrument mode' or in
Menu mode [4 Instr ] and used for network monitoring purposes.
All electrical measured variables are secondary measured values.
Different measured variables are available depending on the
EIB Delta-Meter.
31

Publicité

loading

Ce manuel est également adapté pour:

Ghq 630 7061 p0002