Télécharger Imprimer la page

Eib Commissioning; Lcd Display - ABB i-bus EIB Mode D'emploi

Masquer les pouces Voir aussi pour i-bus EIB:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 19

EIB commissioning

The assignment of the physical addresses, group addresses and
parameter settings is carried out using the ETS program
(EIB Tool Software).
A detailed description of the available EIB application software
and parameter settings can be found in the "User Manual
EIB Delta-Meter Electricity Meters".

LCD display

Displayed energy: The energy is displayed with a resolution of
0.1 kWh (kvarh). In 'Alternative mode', the consumption value is
shown with an additional decimal place after the point,
e.g., 0.01 kWh (kvarh). The displayed energy is a secondary
measured value for transformer rated meters.
In the case of the combination meters, the displayed consumption
value alternates approx. every 6 seconds between active and
reactive power. The type of value is indicated by the unit of
measurement, i.e., kWh or kvarh.
In the case of the tariff meters, the displayed consumption value
also alternates approx. every 6 seconds between each of the
four tariffs and the total.
Power indicators: The LCD display ([A], [R]) and the LED power
indicator flash at a rate of:
– Direct connected meter
1000 Imp/kWh (kvarh)
– Transformer rated meter
5000 Imp/kWh (kvarh)
Note: The measurement of energy consumption takes place in
all display and programming modes. In the event of
voltage failure or disconnection of the device, the current
measured consumption value is maintained, in spite of the
LCD display being inactive.
26
In addition to the energy consumption values, the multifunctional
LCD display shows the user the parameters outlined below.
Voltage indicators
Device OK
L1, L2, L3*
or
Active power
indicator
ERROR
Mode indicator:
No arrow
= Normal mode
Arrow lights up = Alternative mode
Arrow flashes = Instrument mode
Tariff indicator s: (only tariff meter)
No symbol
= Total of all tariffs is displayed.
TX flashes alone
= Tariff X is active and displayed.
TX flashes, TY lights up = Tariff X is active, tariff Y is displayed.
* In the case of three-wire polyphase meters, only voltage
displays L1 and L3 normally light up.
27
"Hand" lights up
(Push putton
Reactive
action is expected)
power indicator
Unit of
measurement
Function indicator:
Arrows rotate at a constant speed,
if the current lies at least one phase
above the starting current

Publicité