The following table describes the format and type of the
measured variable.

Measured variables

Unit
Active power
W
L1, L2, L3, Σ
kW
2
Reactive power
var
L1, L2, L3, Σ
kvar
Voltage
V
L1-N, L2-N, L3-N
(L1-L2, L2-L3)1
Current L1, L2, L3
A
Power factor
, Σ
2
(L1, L2, L3)
Frequency
Hz
1
2
For three-wire meters
Only combination meters
Up to 24 electrical measured variables can be displayed in
Menu mode [4 InStr ], depending on the EIB Delta-Meter.
Button
Number Display/comment
Normal mode (starting position).
S
x 1
[3 Error ]
Sc
x 1
[4 InStr ]
S
x 1
Electrical measured variables are displayed
automatically.
Sc
x n
Scrolls manually through the individual
measured variables.
x 1
Back to [4 InStr ]
LSc
x 1
Back to Normal mode.
LSc
32

Error codes

Once the installation self-test has been carried out, possible
Example
errors are displayed in Menu mode [3 Error ] as installation error
codes.
P1 1250 W
P2 14.50 kW
A detailed description of the error codes can be found in the
P3 35 VAr
"User Manual for EIB Delta-Meter Electricity Meters".
Pt 1.50 kVAr
Error 100, 101, 102:
U1 230.4 V
Phase voltage (L1, L2, L3) is not available.
Note: Phase voltage is not connected.
A3 22.93 a
Error 103, 107, 111:
Pf1 0.95
Phase voltage (L1, L2 L3) lies above the given maximum value.
Caution: Risk of damage.
Fr 50.03
Note: Meter has the wrong nominal voltage value for this
application. Wrong voltage transformer.
Error 104, 108, 112:
Phase voltage (L1, L2, L3) lies below the given minimum value.
Note: Meter has the wrong nominal voltage value for this
application. Wrong voltage transformer.
Error 105, 109, 113:
Phase current (L1, L2, L3) lies above the given maximum value.
Note: Transformer ratio has been set incorrectly. Meter has the
wrong nominal current value for this application.
Error 115, 116:
System frequency lies outside the given range (45 – 65 Hz).
Disconnect the voltage immediately.
33