Putting Into Operation; Maintenance/Servicing; Repairs / Overhaul; Modifications - Eaton CROUSE-HINDS GHG 981 Série Mode D'emploi

Distributions de prises de maintenance et de réparation
Masquer les pouces Voir aussi pour CROUSE-HINDS GHG 981 Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fig. 2 External earth connection
To ensure the required minimum degree of
protection, the cover screws shall be tightened
down.
Overtightening may impair the degree of
protection.

6.6 Putting into operation

Prior to putting the apparatus into operation, the
tests specified in the relevant national regula-
tions shall be carried out.
In addition to this, the correct functioning and
installation of the apparatus in accordance with
these operating instructions and other applicable
regulations shall be checked.
Warning: The maintenance and repair supply
socket distribution may only be put into
operation if a "hot work permit" has been
issued and if it has been ensured that no
potentially explosive gas atmosphere is
present!
If, when the socket distribution is put into
operation, the ELCB (RCD) trips immediately,
check the connected consumer units for an earth
fault. Eliminate any connections or insulation
faults between the neutral and the PE wire.
Check the plug for any damage before inserting
it into the socket.
The user must ensure that a uniform equipoten-
tial earth applies throughout when the plug and
socket system is being operated.
The incorrect installation and operation of
the maintenance and repair supply socket
distributions can entail the loss of warranty.
14
Maintenance and repair supply socket distributions, GHG 981
7

Maintenance/Servicing

The relevant national regulations which apply
Inner wall of
to the maintenance/servicing of electrical
the enclosure
apparatus in explosive atmospheres, shall be
Internal
observed (IEC/EN 60079-17).
earth plate
Before opening the enclosure, make sure that
the device is disconnected from the voltage,
or take appropriate protective measures.
Internal earth
The required maintenance intervals depend on
connection
the specific application and shall be, determined
by the user dependent on the conditions of use.
The white test button "T" of the ELCB (RCD)
shall be operated once a month in the switched
on state. The ELCB (RCD) shall trip when the
test button is actuated (blue switch jumps to
"O" position).
If this is not the case, the protective function is
no longer guaranteed and the ELCB (RCD) shall
be replaced.
Warning: In the case of live socket distribu-
tions and when the enclosure cover is open,
the switching-on of the MCB or the function
test of the ELCB (RCD) shall be carried out
with special care by specialized personnel!
During servicing, special attention shall be given
to checking the parts on which the explosion
protection depends (e.g. intactness of the
flameproof components, the enclosure, the
seals and cable entries).
If, in the course of servicing, it is ascertained,
that repairs are necessary, section 8 of these
operating instructions shall be observed.
8

Repairs / Overhaul /

Modifications

Only original COOPER CROUSE-HINDS /
CEAG parts shall be used for carrying out
repairs.
In the event of damage to the flameproof
encapsulation, replacement of the respective
components is mandatory. In case of doubt,
the respective apparatus shall be sent back
to the manufacturer for repair.
Repairs that affect the explosion protection
may only be carried out by COOPER CROUSE-
HINDS / CEAG or by a qualified electrician in
compliance with the respective national
regulations (IEC/EN 60079-19).
EATON's Crouse-Hinds Business
Components may only be replaced by compo-
nents of the same type (electrical ratings and
mechanical size).
When replacing these individual built-in
components (safety switch, ELCB (RCD's), MCB,
flange sockets, etc.), section 6.2 "Opening
apparatus / Electrical connection" shall be
observed.
Modifications to the device or changes to its
design are not permitted.
9

Disposal / Recycling

The respective valid national regulations for
waste disposal shall be observed when
disposing of apparatus.
To facilitate the recycling of individual parts, parts
made of moulded plastic shall bear the marking
for the type of plastic used.
The product range is subject to changes and
additions.
E