Supply Socket Distributions Ghg 981 - 80A (4 Pole) - Eaton CROUSE-HINDS GHG 981 Série Mode D'emploi

Distributions de prises de maintenance et de réparation
Masquer les pouces Voir aussi pour CROUSE-HINDS GHG 981 Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

The safety switch of the maintenance
and repair supply socket distribution
shall be safeguarded against unau-
thorized use by means of a padlock (padlock
shackle
Ø = 4-6 mm, see page 12, Fig. 1).
The cover cannot be removed when the
safety switch is in the OFF position.
Operation of supply socket distributions is
only permitted if a
"Hot Work Permit"
has been granted.
Before switching on, ensure that there is no
potentially explosive gas atmosphere.
Maintenance and repair supply socket distribu-
tions, GHG 981 0043 / 80A (4 pole)
Dimensions in mm
X = Fixing dimensions
271
X 247
7
33
Maintenance and repair supply socket distributions, GHG 981

1.3 Supply socket distributions GHG 981 - 80A (4 pole)

Marking acc. to 2014/34/EU and directive:
EC-type examination certificate:
Rated voltage:
Rated current:
Back-up fuse:
Switching capacity AC 3:
Perm. ambient temperature:
other temperatures possible for special versions.
Perm. storage temperature in original packing: -20° C to +40° C
Protection category acc. to EN/IEC 60529
with closed and secured hinged cover, as well
as correctly inserted CEAG plugs:
Insulation class acc. to EN/IEC 61140:
Cable entry (standard version):
Suitable cables and test torques of the pressure screw
Cabel entry:
seel 1+2
(Ø mm / Nm)
seel 2
1
(Ø mm / Nm)
Test torque for screw in thread cable entry (Nm) 3.0
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use the
combination of sealing 1 + 2 for the intermediate region.
(2)
When selecting the seal rubber, ensure that the pressure screw can be tightened when carrying out any future
maintenance work on the cable entry.
Supply terminal:
Test torques:
Cover screws
Terminals
Weight (standard version):
230
200
136
1 1
EATON's Crouse-Hinds Business
min.
1
2
(1)(2)
max.
min.
2
(2)
max.
Wiring diagram
GHG 981 0044 / 80A (4 pole)
80 A gG
external
external
<I
L1/L2/L3
0 1
30° 90°
32 A
I> I> I>
IEC 60309
32 A 480-500 V AC
4-pole.; 7h
II 2 G Ex e d II C T6
PTB 00 ATEX 1100X
up to 500 V, 50/60 Hz
max. 80 A
max. 80 A gG
500 V / 80 A
-20° C to +40° C (standard version)
IP 66 (standard version)
I - is complied with by the devices
1xM40 +1xM25
M25
M40
10.0 / 2.3
19.0 / 3.3
13.0 / 2.6
22.0 / 5.5
13.5 / 1.5
22.0 / 3.3
15.0 / 2.3
28.0 / 6.7
7 .5
2 x 4 - 16 mm²
2.5 Nm
2.5 Nm
ca. 8.90 kg
PE
2 A
32 A
I> I> I>
IEC 60309
32 A 480-500 V AC
4-pole.; 7h
E
11

Publicité

Table des Matières
loading

Table des Matières