The safety switch of the maintenance
and repair supply socket distribution
shall be safeguarded against unau-
thorized use by means of a padlock (padlock
shackle
Ø = 4-6 mm, see page 12, Fig. 1).
The cover cannot be removed when the
safety switch is in the OFF position.
Operation of supply socket distributions is
only permitted if a
"Hot Work Permit"
has been granted.
Before switching on, ensure that there is no
potentially explosive gas atmosphere.
Maintenance and repair supply socket distribu-
tions, GHG 981 0043 / 80A (5 pole)
Dimensions in mm
X = Fixing dimensions
10
Maintenance and repair supply socket distributions, GHG 981

1.2 Supply socket distributions GHG 981 - 80A (5 pole)

Marking acc. to 2014/34/EU and directive:
EC-type examination certificate:
Rated voltage:
Rated current:
Back-up fuse:
Switching capacity AC 3:
Perm. ambient temperature:
other temperatures possible for special versions.
Perm. storage temperature in original packing: -20° C to +40° C
Protection category acc. to EN/IEC 60529
with closed and secured hinged cover, as well
as correctly inserted CEAG plugs:
Insulation class acc. to EN/IEC 61140:
Cable entry (standard version):
Suitable cables and test torques of the pressure screw
Cabel entry:
seel 1+2
min.
1
2
(Ø mm / Nm)
max.
seel 2
min.
1
2
(Ø mm / Nm)
max.
Test torque for screw in thread cable entry (Nm) 3,0
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use the
combination of sealing 1 + 2 for the intermediate region.
(2)
When selecting the seal rubber, ensure that the pressure screw can be tightened when carrying out any future
maintenance work on the cable entry.
Supply terminal:
Test torques:
Cover screws
Terminals
Weight (standard version):
80 A gG
external
L1/L2/L3 / N /
80 A
0 1
30° 90°
80 A
<I
63 A
63 A 230/400 V AC
EATON's Crouse-Hinds Business
II 2 G Ex e d IIC T6
PTB 00 ATEX 1100X
bis 500 V, 50/60 Hz
max. 80 A
max. 80 A gG
500 V / 80 A
-20° C to +40° C (standard version)
IP 66 (standard version)
I - is complied with by the devices
1xM50 + 1xM25
M25
10,0 / 2,3
(1)(2)
13,0 / 2,6
13,5 / 1,5
(2)
15,0 / 2,3
2 x 4 - 25 (1 x 35mm² with cable lug)
2.5 Nm
3.5 Nm
ca. 16.20 kg
Wiring diagram
GHG 981 0043 / 80A (5 pole)
PE
2 A
32 A
I> I> I>
I> I> I>
IEC 60309
IEC 60309
32 A 230/400 V AC
5-pol.
5-pol.
M50
24,0 / 6,0
28,0 / 7 ,0
28,0 / 5,0
35,0 / 7 ,0
7 ,5
16 A
16 A
I> I> I>
I>
IEC 60309
DIN 49440
16 A 230/400 V AC
16 A 230 V AC
5-pol.
Earthing contact.
E