Remote parameterisation of system bus devices

If controllers are linked via the system bus (CAN), remote parameterisation of all other
nodes of the system bus is possible from a central point in the network.
For this purpose, the "Remote para" menu can be used:
Step
1.
Select menu 3, "Remote para"
2.
Change to the code level
3.
Change to the parameter level
4.
Set the node address of the
system bus node the remote
parameterisation is to be carried
out for
5.
Change to the code level
6.
Set parameters
7.
Carry out remote
parameterisation for more
system bus nodes if required
Do not forget to switch off remote parameterisation after completion of your settings:
8.
Select menu 3, "Remote para"
9.
Change to the code level
10.
Change to the parameter level
11.
Switch off remote
parameterisation
Remote parameterisation is completed.
EDK82ZBC DE/EN/FR 4.0
Parameterisation 8200 vector/8200 motec
Remote parameterisation of system bus devices
Key
sequence
z y Z Y
Z
V
z
A
T V
B
V
A
V
B
z y Z Y
Z
V
y
l
Action
Change to the "Remote para" menu using
the arrow keys
Display of code C0370 "CANremot para"
Display of the current parameter value:
"0" = OFF
Select node address
Display of "Nodexx"
Confirm node address
Display of the operating level
Display of C0370 "CANremot para"
All settings are redirected to the selected
system bus node
Restart the process with step 1.
Change to the "Remote para" menu using
the arrow keys
Display of code C0370 "CANremot para"
Display of the node address activated last,
"Nodexx"
Set "0" = OFF
7
75