Transmit parameter sets
Parameter settings can be easily copied from one standard device to another using the
keypad.
For this purpose, use "Param managm" in menu 7:
Copying parameter sets from the standard device into the keypad
Step
1.
Connect the keypad to
standard device 1
2.
Inhibit controller
3.
Select submenu 7.1,
"Load/Store", from "Param
managm" in menu 7
4.
Change to the code level
5.
Change to the parameter level
6.
Select the correct copy function
l
Copy all available parameter sets (PAR1 ... PAR4, if required FPAR1) into the keypad:
– Standard device with
function module
application I/O,
INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen
– Standard device with all
other function modules
l
Only copy the module−specific parameter set FPAR1 into the keypad:
– Only possible with
standard devices
including function
module INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen:
EDK82ZBC DE/EN/FR 4.0
Parameterisation 8200 vector/8200 motec
Key sequence
S
z y Z Y
Z
V
z
z
l
Transmit parameter sets
Action
The drive coasts
Use the arrow keys to change to the
"Load/Store" submenu
Display C0002 "Param managm"
Display "0" and "READY"
The settings stored in the keypad are
overwritten.
Copy PAR1 ... PAR4 and FPAR1:
ð
Set "80" "F1&PAR1−4−>Key"
Copy PAR1 ... PAR4:
ð
Set "20" "PAR1−4−>Keypad"
Copy FPAR1:
ð
Set "50" "FPAR1−>Keypad"
7