Bit 0; Bit 1; Bit 2; Bit 3 - S+S Regeltechnik HYGRASGARD RFTF-Modbus Notice D'instruction

Masquer les pouces Voir aussi pour HYGRASGARD RFTF-Modbus:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

G
®
HYGRASGARD
READOUT IN THE DISPL AY
By default, the first lines indicate the following measurements with the corresponding units cyclically and consecutively:
temperature in °C, relative humidity in % r.H. (Resolution: 1/10 °C or 1/10 % r.H.)
The Modbus interface can be used to program an alternative output variable instead of the standard display:
dew point (in °C), mixture ratio (in g ⁄ kg), absolute humidity (in g ⁄ m
relative humidity (in %), temperature (in °C) or setpoint potentiometer (in %)
In this case, the first line indicates the value and indexwhile the second line indicates the corresponding unit statically.
The index indicates the display type, e.g. dew-point temperature (see the table "Function 06 Write Single Register").
The Modbus interface allows the display screen to be individually configured, both in the 7 and 14 segment range and in
the dot-matrix range. This means that messages such as those from the PLC can be displayed.
For the individual display, the register 4x0001 (physical value displayed) must contain the value 10.
The registers 4x0002 to 4x0012 contain information about the characters and segments to be displayed.
The dot-matrix area is also programmable in the default setting (register 4x0001 contains the value 0).
In this case, the current measured value is automatically displayed in the 7-segment area.
Composition of Segment Pattern (Register 4x0005)
Bit 0 ...... Dot A
Bit 1 ...... Dot B
Bit 2 ...... Dot C
Bit 3 ...... Dot D
Bit 4 ...... Dot DP
Bit 5 ...... Percent
Bit 6 ...... - -
Bit 7 ...... - -

Bit 8 ...... - -

Bit 9 ...... - -

Bit 10 .... - -

Bit 11 .... - -
Bit 12 .... - -
Bit 13 .... - -
Bit 14 .... - -
Bit 15 .... - -
Composition of 14-Segment Pattern (Register 4x0003 and 4x0004)
Bit 0 ...... A
Bit 1 ...... B
Bit 2 ...... C
Bit 3 ...... D
Bit 4 ...... E
Bit 5 ...... F
Bit 6 ...... G
Bit 7 ...... G'
Bit 9 ...... I
Bit 10 .... J
Bit 11 .... K
Bit 12 .... L
Bit 13 .... M
Bit 14 .... - -
Bit 15 .... - -
RFTF - Modbus | Configuration
Reading:
13.8
1
Index:
Unit:
°C
Dot A
Dot B
Dot Matrix
H
A
F
G
E
M
D
3
), enthalpy (in kJ ⁄ kg),
Dot DP
Dot C
A
B
I
J
B
G'
C
L
K
17
Dot D
Percent
E
F
G
Example for characters
Degrees Celsius (°C)
14-Segment 1:
14-Segment 2:
227
57
(Register 4x003)
(Register 4x004)
14-Segment 2

Publicité

Chapitres

Table des Matières
loading

Table des Matières