7.2.
installation onto the pipe
danger
Risk of injury due to high pressure in the installation.
•
Stop the circulation of fluid and release the pressure before
loosening the fitting.
Risk of injury due to high fluid temperatures.
•
Use safety gloves to handle the fitting.
•
Stop the circulation of fluid before loosening the fitting.
Risk of injury due to the nature of the fluid.
•
Respect the prevailing regulations on accident prevention and safety
relating to the use of aggressive fluids.
26
Type S020
Installation
7.2.1.
Recommandations on installing the
S020 fitting on the pipe
→
To measure the pH or the oxidation reduction potential, install
a U-shaped bypass in order to prevent the electrode drying out
and to allow calibration without stopping the process.
Fig. 7.2: Installation of the bypass fitting
→
For measuring the flow, install the fitting on the pipe in such a
way that the minimum distances upstream (10xDN) and down-
stream (3xDN) are respected, as shown in fig. 7.3.
Direction of fluid flow
10 x DN
Fig. 7.3: Minimum distances upstream and downstream
English
3 x DN