7
Commissioning
Vector control
16.
If necessary, select more
parameters
17.
Go to the menu
A Check the fan monitoring
setting under code C0608:
– for 8200 motec 0.25...0.37
kW and 0.55...2.2 kW:
C0608 = 0! (default setting)
– for 8200 motec 3...7.5 kW:
C0608 =1 or C0608 = 2!
Stop!
Function must be
activated during
commissioning!
Otherwise, the
controller may be
destroyed through
overheating!
– for all other controllers:
C0608 = 0 ! (default
setting)
B Select additional functions via
codes, if necessary.
When all settings are complete:
18.
Select the setpoint
19.
Enable the controller
20.
The drive should now be running.
110
Activate e.g. JOG frequencies
(C0037, C0038, C0039) or motor
temperature monitoring (C0119)
ALL
E.g. via potentiometer at
terminals 7, 8, 9
EDK82MV222 DE/EN/FR 8.0
X3
20
28
misc002
Terminal X3/28 = HIGH
If the drive does not
start, press u in
addition