Table 2 Inverter Mode Specifications
MODEL
Rated Output Power
Output Voltage Waveform
Output Voltage Regulation
Output Frequency
Peak Efficiency
Overload Protection
Surge Capacity
No Load Power Consumption
Table 3 Battery Specifications
MODEL
Energy
Nominal Voltage
Full Charge Voltage (FC)
Typical Capacity
Max Continuous Discharging
Current
Max Discharging Current
Protection
Max Charge Current
Inner Resistance
Lifecycle
60
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com Hot Line –
Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 10 24 AA 59 203 08
WATTSON Moov 1200
1.2 KVA/ 1.2 KW
Pure Sine Wave
5s@≥130% load; 10s@105%~130% load
2* rated power for 5 seconds
WATTSON Moov 1200
768 Wh
25.6 VDC
28 VDC
≥2500 cycles, 0.5C charging/ discharging ≥50%@EOL 100%
WATTSON Moov 2500
2.5 KVA/ 2.5 KW
230 Vac ± 5%
50 Hz
93%
<35 W
WATTSON Moov 2500
1536 Wh
51.2 VDC
56 VDC
30 Ah
60 A
65 A
BMS
30A (1C)
≦0.6m ohm
DoD