M1 opening delay
Adjust the delay in starting the opening manoeuvre for M1 with respect to M2.
[SET TIME]
M2 closing delay
Adjust the delay in starting the closing manoeuvre for M2 with respect to M1.
[SET TIME]
Pre-fl ashing time
Set the time for which the beacon is activated before each manoeuvre.
[SET TIME]
Electric lock time
Adjust the electric lock release time after an opening or closing command.
[SET TIME]
Thrust time
Adjust the gearmotor closing thrust time after an opening or closing command.
[SET TIME]
Partial opening time
Adjust M2 opening time.
[SET TIME]
Slowdown time
Set the slowdown time before each limit switch.
This function appears only with the [Op.LS-Cl.Slow.] or [Slow.] parameters from the [Confi g] function.
[SET TIME]
New user
Register up to a maximum of 250 users and assign a function to each one.
The operation can be carried out by using a transmitter or another control device. The boards that manage the
control devices (AF - R700 - R800) must be inserted into the connectors.
[USERS]
Edit name
Change the username or associated number.
[USERS]
[Open delay M1]
[Cl.delay M2]
[Pre-fl ashing T.]
[Lock time]
[Thrust T.]
[Part. open]
[Slow. time] function
[New user]
[Edit name]
from 0 to 10 seconds (Default 2 seconds)
from 0 to 60 seconds (Default 2 seconds)
from 1 to 60 seconds (Default 5 seconds)
from 1 to 5 seconds (Default 2 seconds)
from 1 to 10 seconds (Default 1 second)
from 5 to 60 seconds (Default 10 seconds)
[OFF]
from [0 s] to [30 s] (Default 5 s)
[Deactivated]
[2-7] (Step-by-step or sequential control)
[Open]
[B1-B2]
[2-3P] (Pedestrian or partial opening)