Mechanical installation
Regenerative power supply modules EMB9341 and EMB9342
Mounting of EMB9341-C / EMB9342-C with "cold plate" technique
4.2.4
Mounting of EMB9341-C / EMB9342-C with "cold plate" technique
Mounting in "cold plate" technique is only possible with the regenerative power supply
module EMB9341-C or EMB9342-C:
Application
The"cold plate" variant is used mainly for the following applications:
Application of cooling units without blower
ƒ
– e.g. an intense pollution of the cooling air prevents the operation of blowers, since
it would have a negative effect not only on the correct functioning, but also on the
operable life.
Use of the controller directly in the machine with reduced mounting depth
ƒ
– Constructional elements of the machine take over the cooling function
The drive concept provides common cooling units (water coolers, forced-air coolers,
ƒ
etc.) for all controllers.
Requirements on the collective cooler
Collective coolers which can use different coolants (air, water, oil, etc.) can dissipate the
power loss of the regenerative power supply.
In addition to the features required by the user, the following features are important for
safe operation:
Good thermal contact with the collective cooler
ƒ
– Minimum contact surface of the collective cooler with the regenerative power
supply = surface of the cold plate of the regenerative power supply
– Surface flatness of the contact surface approx. 0.05 mm
– Connect collective cooler and cold plate by means of the provided screws.
Comply with the thermal resistance R
ƒ
cooler) acc. to table. The values apply to
– the operation of the regenerative power supply module under rated conditions
(
84).
– a maximum temperature of the cooling plate of 85°C, measuring point: narrow
side of the cooling plate at the mid-height of the regenerative power supply
module.
EMB9341-C
EMB9342-C
94
(transition of cooling plate - collective
th
Power P to be dissipated
P
[W]
v
100
200
Cooling path of cooling plate - collective
cooler
R
[K/W]
th
0.123
0.123