Télécharger Imprimer la page

Lenze EMB934 Serie Manuel D'instructions page 112

Publicité

Les langues disponibles

Les langues disponibles

5
Electrical installation
Regenerative power supply modules EMB9341 and EMB9342
Power connections
Wiring
Stop!
ƒ
ƒ
M6
M5
2
Fig.13-5
PE threaded bolt
Nut M5
Fixing bracket for shield sheet
Serrated lock washer
PE core
Washer
Spring washer
112
The PE connection and the shield sheet at the regenerative power supply
module must always be mounted in the sequence shown. The parts
required are included in the accessory kit.
Do not use the clips for strain relief.
EZN3A0120H012
EZN3A0088H024
0
1
2 3
4
5
6
7
EMB9341
EMB9342
Wiring of the power connections EMB9341 and EMB9342
9
PE
L1
L2
L3
PE
L1'
L2' L3'
8
:
L1
L2
L3 +UG -UG
L3'
L2'
L1' L3.2 L2.2 L1.2
OUTPUT
Synchronization INPUT
Nut M5
Shield sheet
Mains cable
Supply cable of the regenerative power supply
module
Supply cables for devices in the DC-bus connection
Bridges for internal mains synchronisation
(must be removed in case of external mains
synchronisation)
Cable for external mains synchronisation
;
0
PE
PE
<
=
9340vrm019
EDBMB9340 DE/EN/FR 9.0

Publicité

loading

Ce manuel est également adapté pour:

Emb9341Emb9342Emb9343