Maintenance And Monitoring; Using Original Parts; Operating The Filling Station; Important - CEMO 60 Mode D'emploi

Station de ravitaillement essence mobile constituée d'un réservoir en pe à une paroi, équipée d'une pompe electrique 12v
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

1.1.1 Maintenance and monitoring

The filling station must be regularly checked to
ensure it is in a safe condition.
In particular, this check includes:
• a visual inspection for leaks
(seal of filling hose and fittings)
• a function test
• completeness/identifiability of the warning,
mandatory and prohibitory signs on the
installation
• the prescribed regular inspections
(for details see section 6)

1.1.2 Using original parts

Please only use original parts provided or rec-
ommended by the manufacturer. Also take note
of all safety and usage information provided
with these parts.
This applies to:
• spare and wearing parts
• parts for accessories

1.1.3 Operating the filling station

In order to avoid any hazards due to incorrect
operation, the filling station may only be oper-
ated by individuals who
• have read the operating instructions
• have proven their ability to operate the
equipment
• have been assigned to operate the equipment
i

Important!

The operating instructions must be
easily accessible for each user.

1.1.4 Warning notices on the filling station

The warning signs on the installation must
always be affixed and legible.
Signs affixed by the manufacturer:
Ban on fire, naked flames
and smoking
Application:
to the front side of the tank
1.2 Correct use
This mobile petrol filling station is permissible
under ADR 1.1.3.1 a) (private use, max. 60 l
content) and 1.1.3.1 c) ("craftsman regulation").
The filling station is intended for use in changing
locations outdoors or in well ventilated rooms of
Ex-protection zone 2 or higher.
The distances from power source to pump and
from power source to delivery nozzle are speci-
fied in the pump operating instructions and must
be complied with.
The filling of aircraft without the taking of appro-
priate additional measures is not permitted.
Operating temperature range: - 10 °C to + 40 °C
i
Important!
Only a clean medium
may be conveyed.
Correct use concerns, (preferably)
the following liquids:
• fuels with a max. ethanol content of 15 %.
• fuel mixtures.

1.2.1 Petrol trolley to ADR 1.1.3.1 c)

In accordance with ADR 1.1.3.1 c) (called the
"craftsman regulation" in Germany), hazardous
goods may also be transported using containers
without ADR approval.
The following apply to containers in accordance
with ADR 1.1.3.1 c):
• transport only for direct use with self-filling
(i.e. approaching only one filling point and
filling not done by a third party)
• no tagging (stickers) required
• no requirement to equip with a fire extinguisher
• no supporting documents required
• permitted container content: max. 450 l –
the so-called "1000 points rule" also applies
• no repeat testing required
• no reduction in service life
To prevent flames passing into the tank, the
filling pipe is fitted with two flame arresters (with
KITO
arrester elements). These have channels
®
through which gas-air and vapour-air mixes
can flow, thus preventing flames (atmospheric
deflagration) from passing into the tank.
GB
15

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

95

Table des Matières