• To quickly test the unit operation, enable test mode and move out of the sensor's view. Lights should fade to low mode after
5 seconds, and the OFF (if cut off is enabled) after 10 sec.
• If lights still do not turn OFF, call 800.879.8585 for technical support.
False Triggering may occur if the sensor is exposed to high ambient temperature conditions and the unit is set to maximum sensitivity
for PIR detection.
• If this occurs, reduce the PIR sensitivity setting from maximum to a medium point and re-check unit operation.
• If experiencing false triggering during fade down/Off, try increasing the fade time.
Lights do not turn ON:
Check for blinking red LED. If the LED blinks with long pulses, as opposed to short pulses, the sensor has reached its Hold Off setpoint
or Photocell Light Level setpoint.
Lights suddenly turn off and will not come back on:
Check for blinking red LED. If the LED blinks with long pulses, as opposed to short pulses, the sensor has reached its Hold Off setpoint
or Photocell Light Level setpoint.
There is no communication wit th e Sensor Config App:
Perform a power cycle on the FSP-321.
The first time the sensor is installed and powered, there will be 50 seconds of warm-up. The load will turn OFF after the warm up time if
no motion is detected.
Catalog #
FSP-321
Digital High/Low PIR Fixture Integrated Sensor with Bluetooth
FSP-L2
360° lens, up to 44' diameter at 8' height
FSP-L2-S
360° lens, up to 44' diameter at 8' height, with shroud
FSP-L3
360° lens, up to 40' diameter at 20' height
FSP-L3-S
360° lens, up to 40' diameter at 20' height, with shroud
FSP-L7
360° lens, up to 100' diameter at 40' height
FSP-L7-S
360° lens, up to 100' diameter at 40' height, with shroud
FSP-C1
Small collar, for use with FSP-L2 and FSP-L3 lenses
FSP-C2
Large collar, for use with FSP-L7 lens
Sensor is White.
FCC REGULATORY STATEMENTS
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired
operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a
commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to correct the interference at his own expense.
This device complies with FCC and IC safety levels of radio frequency (RF) exposure for Mobile devices.
This device is only authorized for use in a mobile application. At least 20 cm of separation distance between this device and the user's
body must be maintained at all times.
Any changes or modifications not expressly approved by The Watt Stopper Inc. could void the user's authority to operate the equipment.
IC REGULATORY STATEMENTS
This device complies with Industry Canada licence-exempt RSS standard(s).
Operation is subject to the following two conditions: (1) This device may not cause interference, and (2) This device must accept any
interference, including interference that may cause undesired operation of the device.
All manuals and user guides at all-guides.com
OPERATION DURING POWER-UP

ORDERING INFORMATION

4
Description

Publicité

Table des Matières
loading

Table des Matières