DESCRIPTION AND OPERATION
The FSP-321 is a motion sensor that dims lighting from high to low
based on movement. This slim, low-profile sensor is designed for
installation inside the bottom of a light fixture body. The PIR lens
module connects to the FSP-321 through a 1.30" diameter hole in
the bottom of the fixture.
The sensors use passive infrared (PIR) sensing technology that
reacts to changes in infrared energy (moving body heat) within the
coverage area. Once the sensor stops detecting movement and
the time delay elapses lights will go from high to low mode and
eventually to an OFF position if it is desired. Sensors must directly
"see" motion of a person or moving object to detect them, so
careful consideration must be given to sensor luminaire placement
and lens selection. Avoid placing the sensor where obstructions
may block the sensor's line of sight.
The FSP-321 operates at 100-347V Single Phase, as well as
208/230/480VAC phase-to-phase. No power pack is required. It is
designed to be installed in both indoor and outdoor environments.
NOTE: When the FSP-321 is powered up the first time, it will use
factory default parameters to operate. If adjustments are
needed, the Sensor Configuration mobile app must be
used.
PIR Sensor
Motion Indicator
Blue LED
Sensor Protection Cap
NOTE: Remove Cap before use
All manuals and user guides at all-guides.com
Wattstopper
Universal Voltage PIR Fixture Integrated Sensor with Bluetooth low energy technology
Tension universelle, Luminaire avec détecteur IRP intégré avec technologie Bluetooth
basse consommation
Voltaje universal, Sensor PIR para fixturas con tecnología Bluetooth de bajo
consumo
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Reset Button
Light Sensor
®
SPECIFICATIONS
Voltage .............................................. 100–347VAC (single phase)
.......................................208/230/480VAC phase-to-phase
Load Ratings
@ 230–240V ....................... 0–300W Ballast or LED Driver
@ 120V ............. 0–800W Tungsten, Ballast, or LED Driver
@ 277V ............................. 0–1200W Ballast or LED Driver
@347/480V ........................0-1200W Ballast or LED Driver
Motor @ 120V/277V ................................................ 1/6 HP
Class 1 Wiring
Length ...........................................................36" (91.44cm)
Line Voltage ..........................................Line, Neutral, Load
Low Voltage (class 1) ..... Dim + (violet), Dim - (gray), 18AWG
Operating Temperature ....................-40°F (-40°C) to 167°F (75°C)
Tightening Nut Torque ..................................................25–30 in-lbs
Dimensions
Collar ........................................... 1.30" diameter (33.0mm)
Collar height ................................................0.64" (16.3mm)
Body ............1.7" x 3.9" x 1.75" (43mm x 98mm x 44.5mm)
Weight ......................................................................5.5 oz (155 g)
Coverage
FSP-L2 Lens @ 8' height ....................... up to 44' diameter
FSP-L3 Lens @ 20' height ..................... up to 40' diameter
FSP-L7 Lens @ 40' height ................... up to 100' diameter
Adjustments and Features
High Mode ........................................................... 0 V –10 V
Low Mode ...................................................0 V – 9.8 V, Off
Time Delay .............................. 30 seconds, 1 min – 30 min
Cut Off ......................... Disable, 1 min – 59 min ,1 hr – 5 hr
Sensitivity .......................... On-Fix, Off-Fix, Low, Med, Max
Hold Off Setpoint ......................... Auto, None, 1 fc – 250 fc
Ramp Up ........................................Disable, 1 sec – 60 sec
Fade Down .....................................Disable, 1 sec – 60 sec
Photocell Setpoint for On/Off ................................ 1–250 fc
Factory Defaults
High Mode ....................................................................10 V
Low Mode ......................................................................1 V
Time Delay ................................................................. 5 min
Cut Off ........................................................................... 1 hr
Sensitivity .................................................................... Max
Hold Off Setpoint .................................................... Disable
Ramp Up ................................................................. Disable
Fade Down .............................................................. Disable
Photocell Setpoint for On/Off .................................. Disable
OPEN DEVICE for installation in the Listed Enclosure per
Installation Instructions.
Table des Matières
loading

Sommaire des Matières pour LEGRAND Wattstopper FSP-321

  • Page 5: Description Et Fonctionnement

    All manuals and user guides at all-guides.com INSTRUCTIONS EN FRANÇAIS DESCRIPTION ET FONCTIONNEMENT SPÉCIFICATIONS Le FSP-321 est un détecteur de mouvements qui réduit Tension ............100–347 VCA ( monophasé) l'éclairage selon le mouvement. Ce détecteur fin et à profil bas ..........
  • Page 6: Options De Lentilles

    All manuals and user guides at all-guides.com INSTALLATION AVERTISSEMENT COUPEZ L’ALIMENTATION À L’AIDE DU DISJONCTEUR AVANT D’INSTALLER LE CAPTEUR. 1. Déterminez un emplacement de montage approprié à l’intérieur du luminaire qui minimisera la contribution de la lumière électrique à la cellule photovoltaïque du détecteur. Laissez une distance minimale de 5,1 mm (0,2 po) entre l’extrémité...
  • Page 7: Dépannage

    Pour plus d’informations sur les fonctionnalités et le fonctionnement, téléchargez le Guide de l’utilisateur de l’application Config à partir du site Web wattstopper à l’adresse suivante: https://www.legrand.us/ wattstopper.aspx REMARQUE: La radio BLE cesse de diffuser après 7 jours d’activation si aucun mot de passe n’est défini pour l’appareil.
  • Page 8: Informations Concernant Les Commandes

    All manuals and user guides at all-guides.com • Pour tester rapidement le fonctionnement du dispositif, activez le mode test et sortez de la zone couverte par le détecteur. Les lumières doivent diminuer jusqu’au mode bas après 5 secondes et puis s’éteindre (si l’heure limite est activée) après 10 sec. •...

Table des Matières