Les langues disponibles

Les langues disponibles

Liens rapides

No: 27939 – 06/21 rev. 9
Catalog Number • Numéro de Catalogue • Número de Catálogo: FSP-311
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
DESCRIPTION AND OPERATION
The FSP-311 is a motion sensor that dims lighting from high to low
based on movement. This slim, low-profile sensor is designed for
installation inside the bottom of a light fixture body. The PIR lens
module connects to the FSP-311 through a 1.30" diameter hole in
the bottom of the fixture.
The sensors use passive infrared (PIR) sensing technology that
reacts to changes in infrared energy (moving body heat) within the
coverage area. Once the sensor stops detecting movement and
the time delay elapses lights will go from high to low mode and
eventually to an OFF position if it is desired. Sensors must directly
"see" motion of a person or moving object to detect them, so
careful consideration must be given to sensor luminaire placement
and lens selection. Avoid placing the sensor where obstructions
may block the sensor's line of sight.
The FSP-311 has a photocell that can read the light level and
continuously raise or lower the dimming level of the lighting loads,
based on the ambient light and desired light level setting.
The FSP-311 operates at 120V/277V, and 230–240V Single Phase.
No power pack is required. It is designed to be installed in both
indoor and outdoor environments.
NOTE: When the FSP-311 is powered up the first time, it will use
factory default parameters to operate. If adjustments are
needed, the Sensor Configuration mobile app must be used.
PIR Sensor
Motion Indicator
Blue LED
Sensor Protection Cap
NOTE: Remove Cap before use
Wattstopper
Line Voltage PIR Continuous Dimming Fixture Integrated Sensor with Bluetooth
low energy technology
Tension de ligne, Gradation Continue, Luminaire avec détecteur IRP intégré avec
technologie Bluetooth basse consommation
Voltaje de línea, Atenuación Continua, Sensor PIR para fixturas con tecnología
Bluetooth de bajo consumo
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Reset Button
Light Sensor
®
SPECIFICATIONS
Voltage ............................. 230–240V, 50/60Hz, Single Phase: CE
...................................120V/277V, 50/60Hz: UL/cUL Listed
Load Ratings
@ 230–240V ....................... 0–300W Ballast or LED Driver
@ 120V ............ 0–800W Tungsten, Ballasts or LED Driver
Motor @ 120V/277V ................................................ 1/6 HP
@ 277V ............................. 0–1200W Ballast or LED Driver
Wiring Terminals
Line Voltage ..........................................Line, Neutral, Load
................................................................. 16AWG–18AWG
Low Voltage ... Dim + (purple), Dim – (pink), 18AWG–20AWG
Use Solid or Tinned Stranded Copper Conductor
Operating Temperature ....................-40°F (-40°C) to 167°F (75°C)
Tightening Nut Torque ..................................................25–30 in-lbs
Dimensions
Collar ........................................... 1.30" diameter (33.0mm)
Collar height ................................................0.64" (16.3mm)
Body .......3.72" x 1.6" x 1.66" (94.5mm x 41mm x 42.2mm)
Weight ........................................................................2.8 oz (80 g)
Coverage
FSP-L2 Lens @ 8' height ....................... up to 44' diameter
FSP-L3 Lens @ 20' height ..................... up to 40' diameter
FSP-L7 Lens @ 40' height ................... up to 100' diameter
Adjustments and Features
High Mode ........................................................... 0 V –10 V
Low Mode .............................................0 V – 9 V, Disabled
Time Delay .............................. 30 seconds, 1 min – 30 min
Cut Off ....................... Disabled, 1 min – 59 min ,1 hr – 5 hr
Sensitivity ..........................On-Fix, Off-Fix, Low, Med, High
Hold Off .................................. Auto, Disabled, 1 fc – 250 fc
Ramp Up ......................................Disabled, 1 sec – 60 sec
Fade Down ...................................Disabled, 1 sec – 60 sec
Photocell Setpoint for On/Off ................ 1–250 fc, Disabled
Continuous Dimming ............................. 0–250 fc, Disabled
Factory Defaults
High Mode ....................................................................10 V
Low Mode ......................................................................1 V
Time Delay ................................................................. 5 min
Cut Off ........................................................................... 1 hr
Sensitivity ....................................................................High
Hold Off ................................................................ Disabled
Ramp Up ............................................................... Disabled
Fade Down ............................................................ Disabled
Photocell Setpoint for On/Off ................................ Disabled
Continuous Dimming ............................................. Disabled
OPEN DEVICE for installation in the Listed Enclosure per
Installation Instructions.
Table des Matières
loading

Sommaire des Matières pour LEGRAND Wattstopper FSP-311

  • Page 6: Description Et Fonctionnement

    INSTRUCTIONS EN FRANÇAIS DESCRIPTION ET FONCTIONNEMENT SPÉCIFICATIONS Le FSP-311 est un détecteur de mouvements qui réduit Tension ............. 120V/277VCA, 50/60Hz l'éclairage selon le mouvement. Ce détecteur fin et à profil bas ........... 230–240VCA, 50/60Hz, monophasé est conçu pour être installé dans le bas du corps d'un luminaire. Capacité...
  • Page 7: Options De Lentilles

    INSTALLATION AVERTISSEMENT COUPEZ L’ALIMENTATION À L’AIDE DU DISJONCTEUR AVANT D’INSTALLER LE CAPTEUR. 1. Déterminez un emplacement de montage approprié à l’intérieur du luminaire qui minimisera la contribution de la lumière électrique à la cellule photovoltaïque du détecteur. Laissez une distance minimale de 5,1 mm (0,2 po) entre l’extrémité du câblage du détecteur et la paroi du luminaire.
  • Page 8: Fonctionnalité Du Bouton Réinitialisation

    FSP-311 que vous configurez. Pour plus d’informations sur les fonctionnalités et le fonctionnement, téléchargez le Guide de l’utilisateur de l’application Config à partir du site Web wattstopper à l’adresse suivante: https://www.legrand.us/ wattstopper.aspx IMPORTANT: nous vous recommandons de sécuriser le détecteur avec un mot de passe du site.
  • Page 9: Dépannage

    MISE À JOUR DU MICROLOGICIEL DU DÉTECTEUR L’option Mettre à jour le micrologiciel se trouve dans l’écran Options du Détecteur. Lorsque vous sélectionnez cette option, l’écran affiche la version du micrologiciel du détecteur spécifique et la version du micrologiciel inclus avec l’application. Si une version plus récente est disponible et que vous souhaitez mettre à...
  • Page 10: Informations Concernant Les Commandes

    Par la présente, LEGRAND déclare que le type d’équipement radio FSP-311 est conforme à la directive 2014/53 / UE. Le texte complet de la déclaration de conformité UE est disponible à l’adresse Internet suivante: www.legrand.us Ce marquage indique que ce produit ne doit pas être éliminé...
  • Page 16 The Apple logo, iPhone, iPod touch, and iTunes are trademarks © Copyright 2021 Tous droits réservés Legrand. Google Play and the Google Play www.legrand.us of Apple Inc., registered in the U.S. and other countries. © Copyright 2021 Legrand Todos los derechos reservados. logo are trademarks of Google Inc.

Table des Matières