Ordering Information - LEGRAND WattStopper HB300-B L1 Instructions D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

When the power module is installed and power is connected, the load comes ON and stays ON for 50 seconds. This warm-up period
only occurs during installation or after a power failure of 5 minutes or more.
• If the sensor detects occupancy during the warm-up, the lights stay ON as long as it continues to detect motion, plus the Time
Delay.
• If no occupancy is detected during the warm-up, the light turns OFF after the initial 50 second warm-up period.
During the sensor warm-up period, which can last up to a minute after power is applied to the power module (or after a power outage of
5 minutes or more), the load can be either ON or OFF, depending on the status of the relay before the sensor was powered down. After
warm-up, the sensor will open or close the relay to correspond to the occupancy status of the room.
To quickly test the unit, turn the time delay to minimum. Wait for the warm-up period to end. Move out of the sensor's view. Lights should
turn OFF after 15 seconds. Move into the sensor's view. The sensor's Red LED should blink and the lights should turn ON.
Red LED on power module does not blink:
Check sensor wire connections. Verify the red and black wires are tightly secured.
Red LED blinks but lights do not turn ON:
1. Make sure that power to the sensor has been ON continuously for at least one minute, then
a. Turn OFF power to the sensor.
b. Check control wire (blue or violet) connection.
c. Turn ON power to the sensor.
d. The load should come ON. If not, continue with step 2.
2. Check power connections to the light fixture.
Lights will not turn OFF:
1. If there is no motion from people or equipment in the sensor's view but the red LED blinks, look for any nearby source of IR energy
in motion, such as turbulent air from a heating or cooling supply, or other sources. Divert the air supply away from the sensor, or
move the sensor.
2. Verify time delay. The time delay can be set from 15 seconds to 30 minutes. Ensure that the time delay is set to the desired delay
and that there is no movement within the sensor's view for that time period.
3. Check DIP switch 8 setting. If it is ON, it overrides the PIR function and keeps the load ON.
4. Check sensor wire connections. Verify control wire (blue or violet) is secure
Catalog #
HB300-B-L#+
High bay low voltage occupancy sensor consists of:
• HB300-B Power Module
• An HBL# lens (L# indicates the lens number – see COVERAGE GUIDE)
HB300C-B
Designed for colder ambient temperature applications: -40° to 131°F (-40° to 55°C)
HBNB3
Back box with 2 chase nipples and nuts;
• 1 short (0.88") for connection to plastic,
• 1 long (1.24") for connection to metal
HBEM3
Extender module with 2 chase nipples and nuts
• 1 short (0.88") for connection to plastic,
• 1 long (1.24") for connection to metal
BZ-50
Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent
BZ-150
Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent, with Hold-On and Hold-Off capability
BZ-200
Power Pack: 120/277VAC, 50/60 Hz, 20A Ballast/ELV/MLV/Incandescent/LED, 16A, E-Ballast/CFL/Plug Load
BZ-250
Power Pack: 120/277VAC, 50/60 Hz, 20A, Ballast/ELV/MLV/Incandescent/LED, 16A E-Ballast/CFL/Plug Load,
with Hold-On/Hold-Off capability
BZ-250-347
Power Pack: 120/347VAC, 50/60 Hz, 16A Ballast/ELV/MLV/Incandescent/LED/ E-Ballast/CFL, 15A Plug Load,
with Hold-On/Hold-Off capability
All units are White.
IMPORTANT START-UP INFORMATION
TROUBLESHOOTING

ORDERING INFORMATION

4
Description

Publicité

Table des Matières
loading

Table des Matières