HB300-B L1
HB300-B L7
The HB300-B and HB300C-B occupancy sensors are designed for automatic lighting control in warehouse and high bay applications.
They contain a passive infrared sensor (PIR) and are made up of two parts, a Power Module (HB300-B) and a Lens (HBLx). The
coverage area is determined by the lens module. The lenses are interchangeable with any HB3xx series sensor. See the HBLx Lens
Coverage Guide for more information.
The sensor model uses a set of DIP switches to set the time delay and PIR sensitivity. The HB300-B sensors operate at 24VDC and
requires a Wattstopper power pack.
The HB300-B basic model provides a single output to the power pack, which is controlled only by occupancy.
The HB300C-B is for colder ambient temperature applications: -40° to 131°F (-40° to 55°C)
Coverage patterns, density and range, are determined by the type of Lens attached to the HB300-B.
For a complete description of each lens coverage pattern, see the HBLx Lens Coverage Guide.
1. Determine the mounting location appropriate to the features of the power module and the coverage area. Careful consideration must be
given to sensor placement. Avoid placing the sensor where shelving or other obstructions may block the sensor's line of sight.
2. Make sure that you have the appropriate accessories for the sensor mounting configuration. (See Mounting Options.)
3. Assemble any necessary mounting accessories and attach them to the power module, making sure that the flying leads from the
power module are accessible.
4. Connect the line voltage and load wires to the power pack leads as shown in the Wiring Diagram for the unit's application.
• Do not allow bare wire to show.
• Make sure all connections are secure.
5. Attach the Lens to the HB300-B as shown in Fig. 3.
6. Restore power from the circuit breaker.
Wattstopper
High Bay • Low Voltage • Passive Infrared Occupancy Sensor Power Module
Grande hauteur • Basse tension • Infrarouge passif Module d'alimentation
du détecteur de présence
Módulo de alimentación •de bajo voltaje • para el sensor de ocupación
infrarrojo pasivo para áreas de almacenamiento elevadas
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
HB300-B L2/
HB300-B L3
DESCRIPTION AND OPERATION
COVERAGE
INSTALLATION
®
SPECIFICATIONS
Voltage ................................................................... 24VDC
Power Consumption ................................................... 7mA
Power Supply
BZ power pack ................................up to 15 sensors

Publicité

Table des Matières
loading

Sommaire des Matières pour LEGRAND WattStopper HB300-B L1

  • Page 1 Wattstopper ® High Bay • Low Voltage • Passive Infrared Occupancy Sensor Power Module Grande hauteur • Basse tension • Infrarouge passif Module d’alimentation du détecteur de présence Módulo de alimentación •de bajo voltaje • para el sensor de ocupación No: 24160 –...
  • Page 2: Mounting Options

    WIRING White (Neutral) Red (Line) White Power Pack Lighting Load Switch Red (Load) Line Black Common +24VDC Control Output 24VDC Fig. 1: HB300-B Wiring HB300 MOUNTING OPTIONS The HB300-B can be attached either directly to the fixture HBNB3 back box mounting requires a standard 1/2” knockout for surface via the two screw holes provided in the Power Module the chase nipple.
  • Page 3: Time Delay

    The HBEM3 extender module allows threading the wires Fig. 4: Mounting to Fixture with HBNB3 and HBEM3 through its chase nipples and into the fixture for connection. The two sides of the HBEM3 are then snapped together to protect the wires. The short chase nipple is designed to snap HBEM3 Extender into the HBNB3 connection box while the longer chase nipple...
  • Page 4: Ordering Information

    IMPORTANT START-UP INFORMATION When the power module is installed and power is connected, the load comes ON and stays ON for 50 seconds. This warm-up period only occurs during installation or after a power failure of 5 minutes or more. •...
  • Page 5: Description Et Fonctionnement

    INSTRUCTIONS EN FRANÇAIS DESCRIPTION ET FONCTIONNEMENT SPÉCIFICATIONS Les détecteurs de présence HB300-B et HB300C-B sont conçus pour une Voltage ..............24VCC commande de l’éclairage automatique dans les entrepôts et les applications Consommation d'énergie .......... 7 mA de grande hauteur. Ils possèdent un détecteur à infrarouge passif (IRP) Alimentation électrique et sont faits en deux parties, un module d’alimentation (HB300-B) et une Bloc d'alimentation BZ.....
  • Page 6: Options De Montage

    OPTIONS DE MONTAGE Le HB300-B peut être monté soit directement sur la surface du Le montage du coffret arrière HBNB3 nécessite une entrée luminaire via les deux orifices à vis du module d'alimentation défonçable standard de 12,7 mm (1/2 po) pour le manchon de soit en utilisant le coffret arrière HBNB3 et un manchon traversée.
  • Page 7: Dépannage

    RÉGLAGES Le détecteur est préréglé en usine comme suit : Sensibilité PIR (interrupteurs 1 et 2) Moyen 85 % Temporisation (interrupteurs 3-7) 15 minutes Dérogation IRP (interrupteur 8) ARRÊT Sensibilité de l’IRP (interrupteurs 1 et 2) Interrupteur Il peut être nécessaire de régler la sensibilité de l’IRP en cas SENSIBILITÉ...
  • Page 8: Renseignements Pour Les Commandes

    Les lumières ne s’éteignent pas : 1. S’il n’y a aucun mouvement de personnes ou équipement dans le champ de vision du détecteur, mais que la DEL rouge clignote, cherchez une source proche d’énergie infrarouge en mouvement, telle que de l’air turbulent projeté par un appareil de chauffage ou de refroidissement, ou d’autres sources.
  • Page 9: Descripción Y Funcionamiento

    INSTRUCCIONES EN ESPAÑOL DESCRIPCIÓN Y FUNCIONAMIENTO ESPECIFICACIONES Los sensores de ocupación HB300-B y HB300C-B están diseñados Voltaje ..............24 V CC para el control automático de la iluminación en bodegas y aplicaciones Consumo de energía ..........7 mA de montaje alto. Contienen un sensor de infrarrojos pasivo (PIR) y se Fuente de energía componen de dos partes, un módulo de alimentación (HB300-B) y una Fuente de alimentación BZ ..
  • Page 10: Opciones De Montaje

    OPCIONES DE MONTAJE El montaje en la caja posterior HBNB3 requiere un troquel de 12 El HB300-B puede conectarse directamente a la superficie del accesorio de iluminación a través de los dos orificios para mm (1/2 in) estándar para el empalme roscado. La caja viene lista tornillos provistos en el módulo de alimentación o utilizando para el montaje lateral.
  • Page 11: Solución De Problemas

    AJUSTES La configuración de fábrica del sensor es la siguiente: Sensibilidad del PIR (interruptores 1 y 2) Medio 85 % Retardo (interruptores 3 a 7) 15 minutos Anulación del PIR (interruptor 8) APAGADO Sensibilidad del PIR (interruptores 1 y 2) Es posible que sea necesario ajustar la sensibilidad del PIR si hay Interruptor alguna interferencia ambiental que cause activaciones falsas o si la...
  • Page 12: Warranty Information

    No. 24160 – 2/17 rev. 1 © Copyright 2017 Legrand All Rights Reserved. 800.879.8585 © Copyright 2017 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2017 Legrand Todos los derechos reservados.

Table des Matières