7 Installation and electrical connection

Installation and electrical connection should be carried out
in accordance with local regulations and only by qualified
personnel!
WARNING! Risk of personal injury!
The relevant accident precaution regulations must be
observed.
WARNING! Risk of electric shock!
Potential dangers caused by electrical energy must be
excluded.
Local or general regulations [e.g. IEC etc.] and directives
from local energy supply companies are to be followed.
7.1 Installation
• Install pump only after completion of all welding/soldering
and after the pipe system had been thoroughly flushed out.
• Mount the pump in an easily accessible location in order to
facilitate later inspections or exchange.
• When installed in the flow pipe of an open-vented system,
the safety vent must be connected on the inlet side of the
pump.
• Isolating valves should be provided and installed at both suc-
tion and discharge ports of the pump in order to facilitate a
possible pump exchange. They must be located in such a way
to prevent valve spindle leakage from spilling onto the con-
trol module (upper valve turned sideways).
• Install pump free of stress and with the motor shaft horizon-
tally located. For module locations refer to Fig. 3. Other
arrangements on request.
• Directional arrows on pump body and the insulation shell
indicate the direction of flow.
• If the mounting location of the module is to be altered, turn
the motor housing as follows:
Installation and operating instructions Wilo-Stratos ECO
English
23