Product characteristics

7
Installation and electrical con-
nection
7.1

Receipt of the product

7.2

Installation

26

Installation and electrical connection

4.
Filler screw
5.
Drainage screw
6.
Piping or clamp holders
7.
Strainer
8.
Tank
9.
Mains water supply
10. Motor protection switch
11. Lifting hook
ƒ
Multistage vertical-axis centrifugal pump (2 to 16 stages depending on the model).
ƒ
Non-self-priming with "in-line" connections.
ƒ
Shaft sealing with mechanical seal.
ƒ
Integrated thermal motor protection (single-phase version), automatic reset.
ƒ
Condenser integrated into the terminal box (single-phase version).
ƒ
To move the pump, only use straps properly attached to the motor jet rings ≥ 4.2 kw
(Fig. 10).
All installation and electrical connection work must be carried out solely by author-
ised and qualified personnel, in accordance with applicable regulations.
WARNING
Physical injuries
The applicable regulations for the prevention of accidents must be complied with.
WARNING
Risk of electric shock
Hazards from electric current must be prevented.
Unpack the pump and recycle or dispose of the packaging in an environmentally re-
sponsible manner.
The pump must be installed in a dry, well-ventilated location free of frost on a flat, rigid
surface using the appropriate screws.
CAUTION
Risk of damaging the pump
The presence of foreign matter or impurities in the pump housing may affect the
functioning of the product.
It is recommended to perform any welding and soldering work before installing the
pump.
Rinse the circuit completely before installing and commissioning the pump.
ƒ
The pump must be installed in a place easy to access for the purposes of inspection
or replacement.
ƒ
Install the pump on a smooth floor.
ƒ
Installation and connection dimensions (paragraph 5.2).
ƒ
Ensure there is a minimum distance between the motor fan and any surfaces (Fig. 6).
ƒ
For heavy pumps, install a lifting hook (Fig. 1 [11]) above the pump to facilitate its
dismantling.
ƒ
Remove the condensate plugs (Fig. 7 [12]) when the pump is in a condensing envi-
ronment. In this case, the motor protection class IP55 will no longer be guaranteed.