Wiring of UPS and BATTERY CABINET

The electrical hook-up of the EBC to the UPS is part of the installation that is not normally performed by the UPS
manufacturer. For this reason, the indications that follow are to be considered approximate and it is recommended that
the electrical connections are made based on local installation standards.
ATTENTION
The choice of cable type and their cross sections depending on the rated current and their installations must be made as
indicated by the installation standards in force and it is a responsibility of the skilled technician.
Check the UPS installation manual to verify the battery current.
UPS Capacity
10KVA
20KVA
Recommended Cable Size
8AWG/ 8 mm
6AWG/ 16 mm
2
2
STEP 1
42