Electrical installation

Wiring according to EMC

Please observe the following for wiring according to EMC guidelines:
)
Note!
Separate control cables from motor cables.
ƒ
Connect the shields of the control cables and data cables on both sides.
ƒ
The shield for the function module must be connected to the terminal "SH"
(Shield).
Differences in potential between the standard devices can be avoided by
ƒ
using an equalizing conductor with a large cross−section (reference: PE).
Please see the information on wiring according to EMC guidelines in the
ƒ
Operating Instructions for the standard device.
General wiring information
1.
Comply with the DeviceNet bus topology
2.
Bus terminating resistors of 120
l
between CAN−LOW and CAN−HIGH
l
only at the cable ends
Bus cable according to the specification ^ 45.
3.
Do not exceed the permissible bus cable length (see ^ 55).
4.
EDK82ZAFVC010 DE/EN/FR 2.0
Electrical installation
W
each (scope of delivery):
l
Wiring according to EMC
3
43