Connections and wiring
We recommend connecting the charging station in delta networks without
upstream transformer only with single phase. A three-phase connection in
delta networks should only take place with an upstream transformer ("trian-
gle-to-star converter").
Fig. 7-16: Connection to a three-wire IT system with 230 V
7.4
Enable input X1 (except xChargeIn A Series)
The enable input X1 is equipped for use with a potential-free contact. Using
the enable input, it is possible to control the charging station using external
components (e.g. Eaton xComfort Building Automation System, external key
switches, house control, photovoltaic system, ...). The terminal is designed
as a spring-type terminal.
Open
Closed
The use of the enable input must be activated with a DIP switch setting
(DSW1.1 to ON).
For further information see
34
Enable contact
DSW1.1 ON means a charge enable with X1 closed AND correct RFID
authorization.
DSW1.1 OFF means charge enable with X1 closed OR correct RFID au-
thorization.
State of the charging station
Locked
Ready for operation
8.1 DIP switch
settings.
xChargeIn
Installation manual V1.01