Installation instructions, only for experts

5.8. Connecting the heater sensor F1

1. Guide the heater sensor cables through the bushing
connection area
2. Connect the red heater sensor wires (STB) to the terminals labelled "R-R"
in terminal strip
3. Connect the white heater sensor wires (F1) to the terminals labelled "W-W"
in terminal strip
For timed humidity in single-sensor mode, the dummy sensor must be
installed (see 5.12 on page 21).
5.9. Connecting the humidity/temperature sensor FTS2
(optional)
1. Guide the sensor cables through the bushing
nection area
2. Connect the temperature sensor wires to the terminals labelled "FTS2: sw-br"
in terminal strip
a. Connect the black wire to the terminal labelled "sw".
b. Connect the brown wire to the terminal labelled "br".
3. Connect the humidity sensor wires to the terminals labelled "FTS2: gn-or-rt"
in terminal strip
c. Connect the green wire to the terminal labelled "gn".
d. Connect the orange wire to the terminal labelled "or".
e. Connect the red wire to the terminal labelled "rt".

5.10. Connecting the bench sensor F2 (optional)

1. Guide the bench sensor cables through the bushing
connection area
2. Connect the bench sensor wires to the terminals labelled "F2: ws-ws" in
terminal strip
For timed humidity in two-sensor mode (F1 and F2), the dummy sensor
must be installed (see 5.12 on page 21)
.
j
.
f
.
f
.
j
.
h
.
h
.
j
.
h
into the low-voltage
e
into the low-voltage con-
g
into the low-voltage
e
p. 20/38