8 Status messages

Categories of mes-
sages and display
options
General messages
Power-up error (E)
Error messages (F)
taken from/for further information:
Operating instructions
3ADW000055 - chapter 4
The thyristor power converters from the DCS 500B/DCF 500B se-
ries output general messages / power-up errors / error and alarm
messages with the aid of a seven-segment display on the SDCS-
CON-x processor board. The messages appear as codes. In the
case of multi-character codes, the individual letters/digits are
displayed in succession for 0.7 s at a time.
Additionally, in conjunction with the LC display of the CDP 31x dis-
play and control unit, the error and alarm messages and the status
messages are available in plaintext.
They appear only on the seven-segment display of the SDCS-CON-
x processor board.
8
Program not running
.
Normal state, no error/alarm messages
L
Display if a different firmware package is loaded into the
drive
(1) Switch units off and on again electrically; if the error recurs, check the SDCS-
POW-1 and SDCS-CON-x boards, and replace if necessary.
Power-up errors appear only on the seven-segment display of the
SDCS-CON-x processor board. The drive cannot be started up.
E1
Error in ROM test
E2
Error in RAM test
E3
TC connection board missing
(not with software version S21.1xx)
E4
Communication board SDCS-CON-x faulty
E5
No program for closed- and open-loop control in memory
E6
ASIC not OK
E7
Parameter FLASH identification failed
(1) Switch units off and on again electrically; if the error recurs, check the SDCS-
POW-1 and SDCS-CON-x boards, and replace if necessary.
(2) Check communication board, plug on correctly, and replace if necessary.
(3) Reload firmware.
Error messages appear on the seven-segment display of the
SDCS-CON-x computer board as Code F .. and on the LC display
of the CDP 31x display and control unit as text. All error messages
(with the exception of F 17, F 18 and F 44) are (following elimination
of the error concerned) resettable; F 20 is self-resetting, if the
communication function has been restored beforehand. To reset er-
ror messages, the following steps are required:
-
Cancel the ON/OFF and RUN commands
-
Eliminate the cause of the error
-
Acknowledge error with the RESET command at the CDP 31x
panel or by briefly setting the RESET command via binary in-
put/serial interface
-
Depending on the system conditions involved, generate the
ON/OFF and RUN commands anew.
Error messages lead to cancellation of the signal [10910] and to the
drive being completely or partially switched off.
3ADW000177R0200_DCS500B_QuickGuide_edisf_b
Description
Description
Remark
(1)
Remark
(1)
(1)
(2)
(3)
(1)
(1)
I 17