ICAR PQS
Selected parameter
Minimum possible setting
Graph bar of the value-range
When the editing screen is displayed, the parameter setting can be modified with ◄ and ►keys. The screen shows the new
setting, a graphic bar that shows the setting range, the maximum and minimum values, the previous setting and the factory default.
Pressing ◄ + ▼the value decreases faster, while with ▲+ ►the value grows faster.
Pressing simultaneously ◄ + ►, the setting is set to factory default. During the entry of a text string, keys ▲and ▼are used to
select the alphanumeric character while◄ and ► are used to move the cursor along the text string. Pressing keys ▲and
▼simultaneously will move the character selection straight to character 'A'. Press  to go back to the parameter selection. The
entered value is stored.
Press ◄ to save all the settings and to quit the setup menu. The controller executes a reset and returns to normal operation.
If the user does not press any key for more than 2 minutes, the system leaves the setup automatically and goes back to normal
viewing without saving the changes done on parameters.
N.B.: a backup copy of the setup data (settings that can be modified using the keyboard) can be saved in the eeprom memory of
the power factor controller. This data can be restored when necessary in the work memory. The data backup 'copy' and 'restore'
commands can be found in the commands menu. (see chapter 27. Command menu)

20 PARAMETER TABLE

Below are listed all the programming parameters in tabular form. For each parameter are indicated the possible setting range and
factory default, as well as a brief explanation of the function of the parameter. The description of the parameter shown on the
display can in some cases be different from what is reported in the table because of the reduced number of characters available.
The parameter code can be used however as a reference.
Note: The parameters shown in the table with a shaded background are essential to the operation of the system, thus they
represent the minimum programming required for operation.
M01 - UTILITY
P01.01
Language
P01.02
Set clock at system power on
P01.03
LCD contrast
P01.04
Display backlit high intensity
P01.05
Display backlit low intensity
P01.06
Time to switch to low backlighting
P01.07
Return to default page
P01.08
Default page
P01.09
Plant description
P01.01 – Select display text language.
P01.02 – Active automatic clock settings access after power-up.
P01.03 – Adjust LCD contrast.
P01.04 – Display backlight high adjustment.
P01.05 – Display backlight low adjustment.
P01.06 – Display backlight low delay.
P01.07 – Default page display restore delay when no key pressed. If set to OFF the display will always show the last page selected manually.
P01.08 – Default page displayed on power-up and after delay.
P01.09 – Free text with alphanumeric identifier name of specific panel/plant. If a description is set here, it will be shown as title of the home page. The same
description will be used also for identification after remote reporting alarms/events via SMS/E-mail.
M02 – GENERAL
P02.01
CT primary
P02.02
CT secondary
P02.03
Plant type
P02.04
Current reading phase
P02.05
CT polarity
P02.06
Voltage reading phase
Set-up: editing page
Psw (M15)
UoM
Usr
Usr
Usr
%
Usr
%
Usr
%
Usr
s
Usr
s
Usr
Usr
Psw (M15) UoM
Usr
A
Usr
A
Usr
Usr
Usr
Usr
38 / 86
New value entered
Maximum possible setting
Factory default setting
Default
Range
English / Italian / French
Spanish / Portuguese
English
German / Polish / Czech
Russian / Custom
OFF
OFF-ON
50
0-100
100
0-100
25
0-50
180
5-600
60
OFF / 10-600
main
(page list)
(empty)
String 20 chr.
Default
Range
OFF
OFF/1-30000
1
5
5
Three-phase
Three-ph
Single phase
L1
L2
L1
L3
L1 L2 L3
Aut
Aut
Dir
Rev
L1-L2 / L2-L3 / L3-L1
L1-L2-L3
L1-N / L2-N / L3-N / L1-L2-L3
L1-L2-L3-N
rev9 jan19