M19 - MISCELLANEOUS
P19.01 - If set to ON, when switching from AUT mode to MAN mode, steps are disconnected in sequence.
P19.02- Time interval after which it is necessary to perform maintenance.
P19.03– If set to "Always" will count the time in which the controller 8BGA stay lit when set to "Step inserted " count the time in which a pleasant step is
inserted.
P19.04-P19.06 – See P19.02
P19.05-P19.07 – See P19.03
P19.08 -
It defines the number of operations of the steps (considering the step that has the highest count) beyond which the A23 Contactor Maintenace alarm
is generated.
(*) If the controller is installed on the ICAR cabinet
M20 – LIMIT THRESHOLDS (LIMn,n=1...16)
P20.n.01
Reference measurement
P20.n.02
Channel nr. (x)
P20.n.03
Function
P20.n.04
Upper threshold
P20.n.05
Multiplier
P20.n.06
Delay
P20.n.07
Lower threshold
P20.n.08
Multiplier
P20.n.09
Delay
P20.n.10
Idle state
P20.n.11
Memeory
Note: this menu is divided into 16 sections for the limit thresholds LIM1..16
P20.n.01 – Defines to which power factor controller measurements the limit threshold applies.
P20.n.02 – If the reference measurement is an internal multichannel measurement (AINx for example), the channel is defined.
P20.n.03 – Defines the operating mode of the limit threshold. Max = LIMn enabled when the measurement exceeds P20.n.04. P20.n.07 is the reset threshold.
Min = LIMn enabled when the measurement is less than P20.n.07. P20.n.04 is the reset threshold. Min+Max = LIMn enabled when the measurement
is greater than P20.n.04 or less than P20.n.07.
P20.n.04 and P20.n.05 - Define the upper threshold, obtained by multiplying value P20.n.04 by P20.n.05.
P20.n.06 - Upper threshold intervention delay.
P20.n.07, P08.n.08, P08.n.09 - As above, with reference to the lower threshold.
P20.n.10 - Inverts the state of limit LIMn.
P20.n.11 - Defines whether the threshold remains memorized and is reset manually through command menu (ON) or if it is reset automatically (OFF).
M21 – COUNTERS (CNTn,n=1...8)
P21.n.01
Count source
P21.n.02
Channel number (x)
P21.n.03
Multiplier
P21.n.04
Divisor
P21.n.05
Description of the counter
P21.n.06
Unit of measurement
P21.n.07
Reset source
P21.n.08
Channel number (x)
Note: this menu is divided into 8 sections for counters CNT1..8
P21.n.01 - Signal that increments the count (on the output side). This may be the start-up of the 8BGA (ON), when a threshold is exceeded (LIMx), an external
input is enabled (INPx), etc.
P21.n.02 - Channel number x with reference to the previous parameter.
P21.n.03 - Multiplier K. The counted pulses are multiplied by this value before being displayed.
P21.n.04 - Divisional K. The counted pulses are divided by this value before being displayed. If other than 1, the counter is displayed with 2 decimal points.
P21.n.05 - Counter description. 16-character free text.
P21.n.06 - Counter unit of measurement. 6-character free text.
P21.n.07 - Signal that resets the count. As long as this signal is enabled, the count remains zero.
P21.n.08 - Channel number x with reference to the previous parameter.
M22 – ANALOG INPUTS (AINn,n=1..4)
P22.n.01
Input type
P22.n.02
Start of scale value
P22.n.03
Multiplier
P22.n.04
End of scale value
P22.n.05
Multiplier
P22.n.06
Description
P22.n.07
Unit of measurement
Note: this menu is divided into 4 sections for the analog inputs AIN1...AIN4, available with the INP 2AN expansion modules.
P22.n.01 - Specifies the type of sensor connected to analog input. The sensor should be connected to the appropriate terminal for the type selected. See input
module manual.
P22.n.02 and P22.n.03 - Define the value to display for a min. sensor signal, in other words at the start of the range defined by the type (0mA, 4mA, 0V, -5V,
etc.). Note: these parameters aren't used for a type PT100 sensor.
P22.n.04 and P22.n.05 - Define the value to display for a max. sensor signal, in other words at the end of scale of the range defined by the type (20ma, 10V,
+5V, etc.). These parameters aren't used for a type PT100 sensor.
P22.n.06 - Description of measurements associated with analog input. 16-character free text.
P22.n.07 - Unit of measurement. 6-character free text. If the input is type PT100 and the text of the unit of measurement is °F, the temperature will be
displayed in degrees Fahrenheit, otherwise it will be in degrees Celsius.
Psw (M15)
UoM
Default
Psw (M15)
UoM
Default
Usr
OFF
Usr
1
Usr
Max
Usr
0
Usr
x1
Usr
s
0
Usr
0
Usr
x1
Usr
s
0
Usr
OFF
Usr
OFF
Psw (M15)
UoM
Default
Usr
OFF
Usr
1
Usr
1
Usr
1
Usr
CNTn
Usr
Umn
Usr
OFF
Usr
1
Psw (M15)
UoM
Default
Usr
OFF
Usr
0
Usr
x1
Usr
100
Usr
x1
Usr
AINn
Usr
UMn
44 / 86
rev9 jan19
Range
Range
OFF- (misure)
OFF / 1-99
Max – Min – Min+Max
-9999 - +9999
/100 – x10k
0.0 – 600.0
-9999 - +9999
/100 – x10k
0.0 – 600.0
OFF-ON
OFF-ON
Range
OFF-ON-INPx-OUTx-LIMx-REMx
1-8
1-1000
1-1000
(Text – 16 characters)
(Text – 6 characters)
OFF-ON-INPx-OUTx-LIMx-REMx
1-8
Range
OFF / 0..20mA / 4....20mA
0...10V / -5V...+5V / PT100
-9999 - +9999
/100 – x1k
-9999 - +9999
/100 – x1k
(Testo – 16 caratteri)
(Testo – 6 caratteri)