Chapter 11
11.3 Coupling several Renovent Excellent appliances through eBus;
Important:
Because of polarity sensitivity, always connect contacts X1-1 to X1-1 and contacts X1-2 to X1-2.
Never connect X1-1 and X1-2!
A
230 V
B
50 Hz
For M (Master):
Set step number 8 to 0
(= factory setting).
Display shows
ventilation mode 1, 2 or 3.
A
= Multiple switch
B
= 2-Pole connector
M
= Renovent Excellent (Master)
C1 - C* = Renovent Excellent (Slave)
All Renovents have the same air ow rates as the
Renovent set as "Master".
11.4 Connecting RH (humidity) sensor
230 V
50 Hz
30
230 V
50 Hz
M
m³/h
C
D
E
A
B
see §9.2
Renovent Excellent 180
Electric connections accessories
B
C1
For C1 (Slave1):
Set step number 8 to 1
(= Slave 1).
Display always shows
Step
Description
no.
8
eBus address
A = Renovent Excellent 180
B = Control board; to access board , see §9.2 item 1 - 5
C = RH (humidity) sensor
D = The cable that comes with RH sensor;
Cut out an opening in the available grommet for feeding
through the sensor cable
E = Duct "from dwelling"
Step
Description
no.
Switching on
30
RH sensor
31 Sensitivity
A maximum of 10 appliances
linked through eBus
(1 Master + 9 Slaves max.)
B
230 V
50 Hz
C2
m³/h
For C2 (Slave2):
Set step number 8 to 2
(= Slave 2).
Display always shows
(factory
Range
setting
0 = master
0
1 - 9 = slave 1 - 9
Factory
Range
setting
OFF = switched off
OFF
ON = switched on
+2 most sensitive
+1
0
0 basic setting RH sensor
-1
-2 least sensitive
m³/h