Chapter 4

4.1 Description

The appliance comes plug and play and operates fully auto-
matically. The exhausted indoor air heats up the fresh, clean
outdoor air. That saves energy and fresh air is sent to the re-
quired rooms.
The control system has four ventilation modes.

4.2 Bypass function preconditions

Because of its compact design, the appliance is not equipped
with a bypass diffuser but it uses bypass functionality. Bypass
functionality means that the supply fan is switched off when the
der these conditions -undesired- heat recovery does not occur.
Bypass function active
Bypass function not active

4.3 Frost safety

To prevent freezing of the heat exchanger at extremely low
outdoor temperatures, the Renovent Excellent 180 features
frost control. Temperature sensors measure the temperatures
across the heat exchanger and, if an optional preheater is in-
stalled, it will be switched on when required.

4.3 Renovent Excellent Plus version

The Renovent Excellent 180 is also available as "Plus" version.
This version is equipped with a different control board with 2
additional connectors (X14 & X15) with more connection opti-
ons for various applications.
The "Plus" version has a 9-pole connector which is connected
to X15 from the control board. This 9-pole connector is acces-
sible from the top of the Renovent Excellent 180.
The 2-pole connector X14 is accessible after sliding the control
board to the front from the appliance (see §9.2 item 1 - 5). An
additional gland is available at the top of the appliance in "Plus"
version>. That makes it possible to feed a 230 V cable, which
may be connected to connector X14, to outside the appliance.
Always use a gland with strain reliever.
See § 11.1 for more information on the connection possibilities
of connectors X14 and X15.
10
-
-
Bypass function preconditions
- The outdoor temperature is higher than 10°C and
- the outdoor temperature is lower than the indoor temperature in the dwelling and
- the temperature in the dwelling is higher than the temperature set at step no. 5 in the set-
tings menu (set a standard at 22°C)
- The outdoor temperature is lower than 10°C or
- the outdoor temperature is higher than de indoor temperature in the dwelling or
- the temperature from the dwelling is higher than the temperature set at step no. 5 in the set-
tings menu minus the preset temperature at hysteresis (step no. 6); the factory setting for
this temperature is 20°C (22.0°C minus 2.0°C).
Renovent Excellent 180
Dependent on the connected multiple switch, 3 or 4 ventilation
fans is realised independent of the duct pressure.
Optimum performance of this system requires natural supply. It
is assumed that at very high indoor temperatures the user will
automatically open the windows for reasons of comfort. The
number 5, step numbers 6 and step number 7 in the settings
menu (see chapter 13).
That guarantees a proper ventilation balance, also at very low
outdoor temperatures. If, with switched on preheater, the ex-
changer temperature still starts to drop below zero, stepless
unbalance is created in the appliance.
9-pole connector

Operation

-
Feed-through op-
tion for 230V cable
from X14.